Mitsubishi MELSEC Q Series User Manual page 64

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
Device No.
Signal Name
Operating
Y9
condition setting
request
User range
YA
writing request
Channel change
YB
request
Offset/gain
YC
change request
1
Maximum
value/minimum
YD
value reset
request
Error clear
YF
request
1: Q62AD-DGH only
3 - 35
(2)
Output signals
(1) Turn this signal ON when making any of the following settings valid.
• A/D conversion enable/disable setting (buffer memory address 0: Un\G0)
• CH
Average time/Average number of times/Move average/Time constant settings
(buffer memory addresses 1 to 4: Un\G1 to Un\G4)
• CH
A/D conversion starting time setting (buffer memory addresses 5, 6: Un\G5,
Un\G6)
• Averaging process specification (buffer memory address 9: Un\G9)
• Input signal error detection extended/input signal error detection/warning output
settings (buffer memory address 47: Un\G47)
• CH
process alarm upper/lower limit value (buffer memory addresses 86 to 117:
Un\G86 to Un\G117)
• CH
rate alarm warning detection period (buffer memory addresses 118 to 121:
Un\G118 to Un\G121)
• CH
rate alarm upper/lower limit value (buffer memory addresses 122 to 137:
Un\G122 to Un\G137)
• CH
input signal error detection setting value/CH
lower limit setting value (buffer memory addresses 138 to 141: Un\G138 to Un\G141)
• CH
input signal error detection upper limit setting value (buffer memory addresses
142 to 145: Un\G142 to Un\G145)
(2) See the X9 column for ON/OFF timing.
[In offset/gain setting mode]
(1) This turns ON when the value for the adjusted offset/gain settings are registered in the
A/D converter module.
(2) See the XA column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
[In normal mode]
(1) This signal turns ON when the user range is restored.
(2) Refer to the field of XA for the ON/OFF timing.
Refer to Chapter 7 for user range restoration.
(1) This turns ON when changing the channel for which offset/gain settings are to be
performed.
(2) See the XB column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
(1) Turn this signal ON when changing the offset/gain value.
(2) Refer to the field of XC for the ON/OFF timing.
Refer to Section 4.6 for the offset/gain setting.
(1) Turning ON the Maximum value/minimum value reset request (YD) clears the
maximum value/minimum value stored at any of the buffer memory addresses 30 to 37,
62 to 77 (Un\G30 to Un\G37, Un\G62 to Un\G77).
(2) See the XD column for ON/OFF timing.
(1) Turn this signal ON when clearing a write error or input signal error.
(2) Refer to the field of XF or XC for the ON/OFF timing.
Description
input signal error detection
MELSEC-Q
3 - 35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh

Table of Contents