Error Code List - Mitsubishi MELSEC Q Series User Manual

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

8
TROUBLESHOOTING
8 TROUBLESHOOTING

8.1 Error Code List

Error code
(decimal)
The input range is set an illegal value using the
10
intelligent function module switch in GX Developer.
indicates the channel number set incorrectly.
111
Module error at startup.
The setting of the intelligent function module switch
112
5 is other than 0.
The G(P).OGSTOR instruction was executed in the
1
161
offset/gain setting mode.
• The G(P).OGSTOR instruction was executed
consecutively.
2
162
• At the time of offset/gain setting, a set value was
written to the E
The G(P).OGSTOR instruction was executed for the
2
model that differs from the model for which the
163
G(P).OGLOAD instruction had been executed.
The average time setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
3
20
outside the 40 to 5000ms range.
8
indicates the channel number set incorrectly.
The average count setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
3
30
outside the 4 to 500 times range.
indicates the channel number set incorrectly.
The move average count setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
3
31
outside the 2 to 60 times range.
indicates the channel number set incorrectly.
The time constant setting of the primary delay filter
at any of the buffer memory addresses 1 to 4
3
32
(Un\G1 to Un\G4) is outside the 10 to 5000 range.
indicates the channel number set incorrectly.
8 - 1
The following section explains the types of errors that may occur when the A/D
converter module is used, and how to troubleshoot such errors.
If an error occurs in the A/D converter module while writing to or reading data from the
programmable controller CPU, the applicable error code is written to buffer memory
address 19 (Un\G19).
Table 8.1 Error code list (1/3)
Error description
2
PROM 26 or more times.
Processing
Set the correct parameter value in the parameter
setting of GX Developer. (See Section 4.5.)
Turn the power OFF and ON again. If the error
occurs again, the module may be malfunctioning.
Contact the nearest distributor or branch office
with the description of the problem.
Set the correct parameter value in the parameter
setting of GX Developer. (See Section 4.5.)
Do not execute the G(P).OGSTOR instruction in
the offset/gain setting mode.
• Execute the G(P).OGSTOR instruction only once
for one module.
• At the time of offset/gain setting, write a set value
only once at one time.
Execute the G(P).OGLOAD and G(P).OGSTOR
instructions for the same model.
Reset the average time setting to within 40 to
5000ms.
Reset the average count setting to within 4 to 500
times.
Reset the move average count setting to within 2
to 60 times.
Reset the time constant setting to within 10 to
5000.
MELSEC-Q
8 - 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh

Table of Contents