4
SETUP AND PROCEDURES BEFORE OPERATION

4.3 Part Identification Nomenclature

4 - 3
The name of each part of the A/D converter module is listed below.
Name and
Number
appearance
1)
RUN LED
2)
ERR. LED
3)
ALM LED
Check terminals
4)
(Q62AD-DGH only)
External supply
5)
power terminal
(Q62AD-DGH only)
6)
Serial No. plate
1: Check the error code for details.
POINT
When two or more errors have occurred, the latest error found by the A/D converter
module is displayed on the LED.
Displays the operating status of the A/D converter module.
On
: Normal operation
Flickering : During offset/gain setting mode
Off
: 5V power supply interrupted, watch dog timer
error or module exchangeable status during
online module change bled
Displays the error status of the A/D converter module.
1
On
: Error
(A/D conversion continues.)
1
Flickering : Error
(A/D conversion stops.)
Off
: Normal operation
Displays the warning status of the A/D converter module.
On
: An alarm (process alarm, rate alarm) is being
generated.
Flickering : An input signal error is being generated.
Off
: Normal operation
Terminal used to check the analog input current value.
(See Section 4.4.2)
Terminal to connect 24VDC external supply power.
Displays the serial number of the A/D converter module.