Mitsubishi MELSEC Q Series User Manual page 37

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3 - 8
POINT
(1)
Set within the analog input range and digital output range for each input
range.
If these ranges are exceeded, the resolution and accuracy may not fall within
the performance specifications. (Avoid the use of dotted areas of Fig. 3.2.)
(2)
Do not input an analog input current of -30mA or less, or +30mA or more.
Doing so can cause the breakdown of the elements.
(3)
Set the offset/gain values for the user setting range within a range in which
the following conditions are satisfied.
(a) Gain value
(b) { (gain value) - (offset value) } > 9.70mA
(4)
When an analog value that exceeds the range of the digital output value is
entered, the digital output value will be fixed at the maximum or minimum
value.
Analog input
range setting
4 to 20mA
0 to 20mA
4 to 20mA
(Extended mode)
User range setting
(Uni-polar)
20mA, offset value
Digital output value (32 bits)
Minimum
Maximum
-1536
65535
-17536
73535
-1536
65535
0mA
Digital output value (16 bits)
Minimum
-768
-
-768
MELSEC-Q
Maximum
32767
-
32767
3 - 8