3
SPECIFICATIONS
3 - 6
POINT
(1)
Set within the analog input range and digital output range for each input
range.
If these ranges are exceeded, the resolution and accuracy may not fall within
the performance specifications. (Avoid the use of dotted areas of Fig. 3.1.)
(2)
Do not input an analog input voltage of -15V or less, or +15V or more. Doing
so can cause the breakdown of the elements.
(3)
Set the offset/gain values for the user setting range within a range in which
the following conditions are satisfied.
(a) Offset value, gain value setting range: -10 to 10V
(b) { (gain value) - (offset value) } > 3.030V
(4)
When an analog value that exceeds the range for the digital output value is
entered, the digital output value will be fixed at the maximum or minimum value.
Analog input
range setting
1 to 5V
0 to 5V
-10 to 10V
0 to 10V
1 to 5V
(Extended mode)
User range setting
(Uni-polar)
User range setting
(Bi-polar)
Digital output value (32 bits)
Minimum
Maximum
-1536
65535
-65536
-1536
-17536
73535
-1536
65535
-65536
MELSEC-Q
Digital output value (16 bits)
Minimum
Maximum
-768
32767
-32768
-768
-
-
-768
32767
-32768
3 - 6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh

Table of Contents