Warning Output Function - Mitsubishi MELSEC Q Series User Manual

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS

3.2.4 Warning output function

3 - 23
(1)
Process alarm
(a)
If the detected digital output value rose to or above the process alarm
upper upper limit value or fell to or below the process alarm lower lower limit
value and entered the warning output range, the warning output flag (buffer
memory address 48: Un\G48) and warning output signal (X8) turn ON and
the ALM LED is lit to indicate the warning.
(b)
If, after the output of the warning, the detected digital output value fell
below the process alarm upper lower limit value or rose above the process
alarm lower upper limit value and returned to within the setting range, "0" is
stored into the bit position corresponding to the channel number of the
warning output flag (buffer memory address 48: Un\G48).
The warning output signal (X8) turns OFF only when all channels return to
within the setting range.
(c)
When time or count averaging is specified, this function is executed at
intervals of the preset averaging time or averaging count.
When any other A/D conversion system (sampling processing, move
averaging, primary delay filter) is specified, this function is executed at
intervals of the sampling time.
MELSEC-Q
3 - 23