Mitsubishi MELSEC Q Series User Manual page 231

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

APPENDIX
Sequence program
G.OGSTOR instruction
Completion device (D)
Status display device
at completion (D)+1
A/D conversion
completed flag (XE)
APP -11
(1) Functions
(a) Restores the offset/gain values of the user range setting stored in the CPU
to the A/D converter module.
(b) There are two types of interlock signals for the G(P).OGSTOR instruction:
the completion device (D) and the status display device at completion (D) +
1.
1) Completion device
Turns ON in the END processing of the scan where the G(P).OGSTOR
instruction is completed, and turns OFF in the next END processing.
2) Status display device at completion
Turns ON and OFF depending on the completion status of the
G(P).OGSTOR instruction.
Normal completion : Stays OFF and does not change.
Abnormal completion: Turns ON in the END processing of the scan
END processing
END processing
ON
OFF
OFF
OFF
ON
1
OFF
1 When the G(P).OGSTOR instruction is executed, A/D conversion is
not performed. After the completion device (D) turns ON, A/D
conversion starts, the A/D conversion value is stored into the buffer
memory, and the A/D conversion completed flag (XE) then turns ON.
(c) When the offset/gain values are restored, the reference accuracy falls to
about less than three times of the accuracy before that.
(2) Operation error
In any of the following cases, an error occurs and the corresponding error code is
stored into the completion status area (S)+1.
Error code
161
162
163
where the G(P).OGSTOR instruction is
completed, and turns OFF in the next END
processing.
Execution completion of
the G.OGSTOR instruction
Case resulting in operation error
The G(P).OGSTOR instruction was executed in the offset/gain
setting mode.
The G(P).OGSTOR instruction was executed consecutively.
The G(P).OGSTOR instruction was executed for the model that
differs from the model for which the G(P).OGLOAD instruction had
been executed.
MELSEC-Q
END processing END processing
ON
ON Abnormal
completion
Normal completion
1 scan
ON
APP -11