AH500 system configuration
Configuration
Main backplane
Extension backplane
Extension cable
Power supply module
CPU module
Digital I/O module
Analog I/O module
Temperature
measurement module
Motion control module
Network module

2.4 Specifications for Digital Input/Output Modules

2.4.1 General Specifications

Electrical specifications for the inputs on digital input/output modules (The signals passing
through the inputs are 24 V DC signals.)
Model
AH16AM10N
Item
Number of inputs
Removable terminal
Connector type
Input type
Digital input
Input form
Direct current (sinking or sourcing)
Input current
OFF→ON >15 V DC
Action
ON→OFF <5 V DC
level
OFF→ON 10 ms±10%
Response
ON→OFF 15 ms±10%
time
There is one main backplane in an AH500 system.
Four-slot main backplane: AHBP04M1-5A
Six-slot main backplane: AHBP06M1-5A
Eight-slot main backplane: AHBP08M1-5A
Twelve-slot main backplane: AHBP12M1-5A
There are seven extension backplanes at most in an AH500 system.
Six-slot extension backplanes: AHBP06E1-5A
Eight-slot extension backplanes: AHBP08E1-5A
There are four types of lengths.
AHACAB06-5: 60 cm
AHACAB10-5A: 1 m
AHACAB15-5A: 1.5 m
AHACAB30-5A: 3 m
Every backplane needs a power supply module. (The voltages of the
alternating currents which can flow into AHPS05-5A range from 85 V to 264 V,
and the direct currents which can flow from AHPS05-5A are 5 A. AHPS05-5A is
used with a backplane. The voltages of the direct currents which can flow into
AHPS15-5A are 24 V, and the direct currents which can flow form AHPS15-5A
are 1.5 A.)
There is one CPU module in an AH500 system, such as AHCPU5X0-RS2,
AHCPU5X0-EN, AHCPU5X1-RS2, and AHCPU5X1-EN.
Digital I/O modules, analog I/O modules, and temperature measurement
modules can be installed in an AH500 system unlimitedly.
Motion control modules can only be installed on a main backplane.
Network modules can only be installed on a main backplanes. Eight
AH10EN-5A modules at most can be installed on a main backplane, and eight
AH10DNET-5A modules at most can be installed on a main backplane.
However, AHSCM-5A modules can be installed on a main backplane
unlimitedly.
AH32AM10N
AH32AM10N
-5A
-5A
-5B
16
32
32
DB37
block
connector
24 V DC
5 mA
Description
AH32AM10N
AH64AM10N
AH16AP11R
-5C
-5C
-5A
32
64
8
Latch connector
Removable terminal block
24 V DC
3.2 mA
AH16AP11T
AH16AP11P
-5A
-5A
8
8
24 V DC
5 mA