A H 5 0 0 O p e r a t i o n M a n u a l
Error
Code
The network module heart beat of the
16#E290
control mode CPU on the main backplane
slot 0 cannot be detected.
The network module heart beat of the
16#E291
control mode CPU on the main backplane
slot 1 cannot be detected.
The network module heart beat of the
16#E292
control mode CPU on the main backplane
slot 2 cannot be detected.
1 2 - 2 0
Description
Solution
1. Make sure the network cables of the network
modules on the main backplane slot 0 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module's network cable of the
control mode CPU on the main backplane slot 0
is connected to the network port 1, the network
module's network cable of the standby mode
CPU on the main backplane slot 0 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 0 are on the same physical
network.
1. Make sure the network cables of the network
modules on the main backplane slot 1 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module's network cable of the
control mode CPU on the main backplane slot 0
is connected to the network port 1, the network
module's network cable of the standby mode
CPU on the main backplane slot 1 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 1 are on the same physical
network.
1. Make sure the network cables of the network
modules on the main backplane slot 2 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module's network cable of the
control mode CPU on the main backplane slot 2
is connected to the network port 1, the network
module's network cable of the standby mode
CPU on the main backplane slot 2 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 2 are on the same physical
network.