status, the PLC will automatically resume the operation. (Please take care of the
latched auxiliary relays and registers inside the PLC when doing the programming).

Safety Wiring

Since DVP-SS2 is only compatible with DC power supply, Delta's power supply modules
(DVPPS01/DVPPS02) are the suitable power supplies for DVP-SS2. We suggest you
install the protection circuit at the power supply terminal to protect DVPPS01 or
DVPPS02. See the figure below.
AC power supply:100 ~ 240VAC, 50/60Hz
Emergency stop: This button cuts off the system power supply when accidental
emergency takes place.
Power indicator
Power supply circuit protection fuse (2A)
DC power supply output: 24VDC, 500mA
Digital I/O module

Input Point Wiring

There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For
detailed point configuration, please refer to the specification of each model.)
DC Signal IN – SINK mode
Input point loop equivalent circuit
+24V
24G
S/S
X0
X1
[ Figure 5 ]

Output Point Wiring

1. DVP-SS2 has two output modules on it, relay and transistor. Be aware of the
connection of shared terminals when wiring output terminals.
2. Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and
Y5 use C1 common port. See [Figure 7]. When the output points are enabled, their
corresponding indicators on the front panel will be on.
Breaker
AC power supply load
DVPPS01/DVPPS02
DVP-PLC (main processing unit)
DC Signal IN – SOURCE mode
Input point loop equivalent circuit
+24V
24G
S/S
X0
X1
[ Figure 6 ]