Assigning Devices To A Module - Delta Electronics AH500 Operation Manual

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

8.1.2.2 Assigning Devices to a Module

The data in a module needs to be updated constantly. For example, analog signals received by an analog input
module are updated constantly, and converted to data which can be processed by a CPU module. As a result,
the system automatically assigns devices to a module so that the data in the module can be stored. The
devices assigned to a module are displayed in the Input Device Range cell and the Output Device Range cell
on the information list. Please refer to the following example.
AH16AM10N-5A (slot 0)
AH16AM10N-5A is a digital input module which has 16 inputs. The system assigns X0.0~X0.15 to
AH16AM10N-5A so that data received by AH16AM10N-5A can be stored.
AH16AN01T-5A (slot 1)
AH16AN01T-5A is a digital output module which has 16 outputs. The system assigns Y0.0~Y0.15 to
AH16AN01T-5A so that data sent by AH16AM10N-5A can be stored.
AH04AD-5A (slot 2)
AH04AD-5A is an analog input module which has four channels. The system assigns D0~D7 to
AH04AD-5A. After analog signals received by AH04AD-5A are converted into digital data, the digital data
will be stored in D0~D7.
AH16AP11T-5A (slot 3)
AH16AP11T-5A is a digital input/output module which has 8 inputs and 8 outputs. The system assign
X1.0~X1.15 to AH16AP11T-5A so that data received by AH16AP11T-5A can be stored. (X1.0~X1.7 are
actually used.) The system also assigns Y1.0~Y1.15 to AH16AP11T-5A so that data sent by
AH16AP11T-5A can be stored. (Y1.0~Y1.7 are actually used.)
AH20MC-5A (slot 4)
AH20MC-5A is a motion control module. Owing to the fact that the data in AH20MC-5A does not need to
be updated constantly, the system does not assign any device to AH20MC-5A.
8 - 8
C h a p t e r 8 H a r d wa r e C o n f i g u r a t i o n

Advertisement

Table of Contents
loading

Table of Contents