Troubleshooting For Ah10En-5A/Ah15En-5A; Troubleshooting For Ah10Scm-5A/Ah15Scm-5A - Delta Electronics AH500 Operation Manual

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

A H 5 0 0 O p e r a t i o n M a n u a l
Error
Description
code
The conversion into the
16#A019
binary-coded decimal number is
incorrect.
Incorrect division operation (The
16#A01A
divisor is 0.)
16#A01B
General program error
LD/LDI has been used more than
16#A01C
nine times.
There is more than one level of
16#A01D
nested program structure supported
by RPT/RPE.
SRET is used between RPT and
16#A01E
RPE.
There is no M102 in the main
16#A01F
program, or there is no M2 in the
motion program.
The wrong instruction is used, or the
16#A020
device used exceeds the range.

12.3.5 Troubleshooting for AH10EN-5A/AH15EN-5A

Error
Description
code
The IP address of host 1 conflicts
16#A001
with another system on the
network.
The IP address of host 2 conflicts
16#A002
with another system on the
network.
16#A003
DHCP for host 1 fails.
16#A004
DHCP for host 2 fails.
16#A401
Hardware error
The initialization of the system
16#A402
fails.

12.3.6 Troubleshooting for AH10SCM-5A/AH15SCM-5A

Error
Description
code
The setting of the UD Link is
16#A002
incorrect, or the communication
fails.
16#A401
Hardware error
The communication through the
16#A804
communication port is incorrect.
1 2 - 4 8
Remedy
Modify the operation to prevent the abnormal number
from occurring.
Modify the operation to prevent the divisor from being
zero.
Modify the program to make the syntax correct.
Modify the program to prevent LD/LDI from being used
more than nine times.
Modify the program to prevent more than one level of
nested program structure supported by RPT/RPE from
being used.
Modify the program to prevent SRET from being used
between RPT and RPE.
Modify the program so that there is M102 in the main
program, or modify the program so that there is M2 in
the motion program.
Check and modify the program to prevent the wrong
instruction from being used, or check whether the
device used exceeds the device range.
Remedy
1. Contact the network administrator, and check whether
the IP address is correct.
2. Check the module parameter in HWCONFIG.
1. Contact the network administrator, and check whether
the IP address is correct.
2. Check the module parameter in HWCONFIG.
Please contact the network administrator
Please contact the network administrator
Please restore the hardware to the factory setting. If the
error still occurs, please contact the factory.
Please restore the system to the factory setting. If the
error still occurs, please contact the factory.
Remedy
Check the setting in SCMSoft, and download the setting
again.
Please contact the factory.
1. Check whether the communication cable is connected
well.
2. Check the parameter in HWCONFIG, and the
parameter. Download the parameter again.

Advertisement

Table of Contents
loading

Table of Contents