Setting Of Deceleration Time - Mitsubishi FX3G Series User Manual

Melsec-f, positioning control edition, main unit/sink output/source output, line driver output
Hide thumbs Also See for FX3G Series:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Positioning Control Edition
3G
3U
3UC
Built-in Positioning Functions
4.2.8

Setting of Deceleration Time

Set the time required for deceleration from the maximum speed to the bias speed.
If the output pulse frequency is less than the maximum speed, the actual deceleration time will be shorter
than the set deceleration time.
If the variable speed pulse output (PLSV) instruction is used, the set deceleration time is only valid during
acceleration/deceleration (M8338 = ON)
Use the devices shown in the following table to determine the deceleration time for each pulse output
destination device.
Pulse output
destination device
Y000
Y001
*1
Y002
*2
Y003
*1.
Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
connected.
*2.
Devices related to Y003 (pulse output destination) are only valid if two FX
connected to the FX
*3.
Only available for FX
*3
.
Deceleration
Initial value
Time
D8349
D8359
100ms
D8369
D8379
PLC.
3U
/FX
PLC Ver. 2.20 or later and FX
3U
3UC
4.2 Setting of Various Items Regarding Speeds
Setting range
50 to 5,000 ms:
If the value is set to 49 ms or less, the deceleration time will
be automatically set to 50 ms. If the value is set to 5,001 ms
or more, the deceleration time will be automatically set to
5,000 ms.
PLC.
3G
4 Before Programming
PLC is
3G
-2HSY-ADP adapters are
3U
B - 45
A
B
Apx.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc seriesFx3u-2hsy-adp

Table of Contents