2. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or
wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or
initiating operation after installation or wiring work.
Failure to do so may cause electric shock.
• Connect the AC power supply to the dedicated terminals specified in the manual of the PLC main
unit.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the
PLC will burn out.
• Connect the DC power supply to the dedicated terminals specified in the manual of the PLC main
unit.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the
PLC will burn out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the
FX
/FX
PLC main unit with a wire 2 mm
3U
3G
Do not use common grounding with heavy electrical systems (refer to the manual of the PLC main
unit).
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the
main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation
slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Install module so that excessive force will not be applied to I/O connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
• Connect input/output cables securely to their designated connectors.
Loose connections may cause malfunctions.
• Make sure to properly wire the FX
equipment in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the
product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N
• Make sure to properly wire to the European terminal board in accordance with the following
precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the
product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly
stressed.
• Make sure to properly wire to the FX Series terminal blocks in accordance with the following
precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the
product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N
Safety Precautions
(Read these precautions before use.)
2
or thicker.
/FX
Series main unit and FX
3U
3G
m.
m.
(2)
/FX
Series extension
0N
2N
m.
Reference
B-4
B-30
B-78
Reference
B-4
B-30
B-78

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc seriesFx3u-2hsy-adp

Table of Contents