Control System Fault Codes - Genie S-105 Service Manual

Hide thumbs Also See for S-105:
Table of Contents

Advertisement

June 2011
REV A

Control System Fault Codes

How to Clear Boom Safety
Switch Faults
Note: Beginning with software release 3.0, the
boom envelope switches will latch and faults
must be reset in software or through the use of
the TCON LCD. They will not clear by re-powering
the machine.
Note: There are two methods to reset the faults,
by using Web GPI or through the menu available
on the TCON LCD.
Using Web GPI
1 Connect the device containing the WEB GPI
software to the TCON with an RS-232 cable.
2 Select the Safety folder, then the Fault Status
screen.
3 Change any safety switch drop down menus
displaying
to
FAULT
OK
4 Exit Web GPI.
Part No. 102916
. Press
.
SEND
S-100 • S-105 • S-120 • S-125
Section 5 • Diagnostic Codes
Using the TCON LCD
Note: Take care when using this method to avoid
resetting threshold defaults.
1 With the key switch off, press and hold the
button and turn the key switch to the on
position. Release the
seconds and press the
2 Press the
button until
appears.
SWITCH FAULTS
3 Select
, then press the
YES
4 Press the
button until
5 Select
, then press the
YES
Note: This clears all latching faults, not standard
faults.
DIAGNOSTIC CODES
button after five
buttons.
CLEAR ALL SAFETY
button.
appears.
EXIT
button.
5 - 9