Invacare LiNX Service Manual page 43

Controls system for wheelchairs
Hide thumbs Also See for LiNX:
Table of Contents

Advertisement

A
Drive Settings
B
Switched Driving
C
Sleep Settings
D
Lock Settings
E
User Function Navigation
User Function Navigation
F
G
Control Input/Output Settings
1
Risk of injury or damage
– When setting either occupant or attendant as restricted user in user-in-charge-system, consideration needs to be
given to whether benefit outweighs risk, since restricted user is unable to take control from user by activating
power button in emergency.
CAUTION!
Risk of injury or damage
– When setting either occupant or attendant as restricted user in user-in-charge-system, consideration
needs to be given to whether benefit outweighs risk, since restricted user is unable to take control from
user by activating power button in emergency.
A restricted user is an occupant or attendant that is prevented from being user-in-charge once a system is powered
up. By default, there are no restricted users in a LiNX system and both the attendant and the occupant can
request to be user-in-charge at any time by pressing power button. However, for safety and other reasons, it may
1605129-C
Drive Delay At Startup: Allows time delay to be set up between
power-up and driving.
These parameters set veer behavior of drive functions which use
switched inputs, for example a Sip and Puff array. They are unique
to switched driving and independent of forward, reverse and turn
parameters that are used in driving and turning with proportional
inputs, such as joysticks.
Constant Speed Trigger: Sets minimum forward / reverse speed during
veer. If wheelchair is stationary or travelling at a low speed (lower
than Constant Speed Trigger), speed ramps up to Constant Speed
Trigger. Once at Constant Speed Trigger, speed remains constant.
Veer at Low Speed: Provides possibility of maximum veering at lowest
speed. Value must be set greater than Veer at High Speed. Speed at
which Veer at Low Speed is applied is set by Constant Speed Trigger.
Veer at High Speed: Is set to produce less veering at higher speeds.
Value must be less than Veer at Low Speed. Speed at which Veer at
High Speed is applied is set by High Speed Reference.
High Speed Reference: Sets point at which Veer at High Speed is
applied. When wheelchair travels at speeds lower than this, veer
is defined by graph between Veer at Low Speed and Veer at High
Speed. For all speeds higher than High Speed Reference, amount of
veer applied is the same as that set by Veer at High Speed.
Enable Sleep Timeout: Determines whether system goes to sleep
after a period without user activity.
Sleep Timeout Duration: Sets amount of time without user activity
before system goes to sleep, if sleep is enabled.
Enable Joystick Wakeup: Determines whether deflecting joystick can
wake system from sleep.
Enable Lock: Determines whether system can be locked by pressing
power button for four seconds.
Cycle Profiles: User profile menu either cycles or stops at each end.
Parameter determines, if profile menu can cycle around when stepping
through it.
Profile Change uses last function: Sets behavior of system to enter
last used function of profile when particular profile is changed into.
Restricted user priority: Selection for setting system user change
restrictions.
1
Startup Function: Sets default user function on startup as either first
user function of first profile or last used user function.
Refer to 9.8 Enable indirect navigation, page 84 for more information.
Activation Time: Sets maximum time between two button presses
to be recognized as double press and minimum time to detect long
button press.