3.3.6.

C3Sxxx V4

3.3.6.1
Device protection
Caution!
In this chapter you can read about:

Power supply connector X1 for 3AC 400VAC/480VAC-C3S devices................................................31

Braking resistor / high voltage supply connector X2 for 3AC 400VAC/480VAC_C3S devices .........32
Connection of the power voltage of 2 C3S 3AC devices ...................................................................33
Power supply connector X1 for 3AC 400VAC/480VAC-C3S
devices
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which will cause a device error.
Therefore please wait at least 2 minutes after switching off before you switch
PIN
Designation
1
L1
2
L2
3
L3
4
PE
Mains connection Compax3SxxxV4 3AC
Controller type
Supply voltage
Input current
Maximum fuse rating per
device(=short circuit
rating)
* for UL conform operation (see page 18): MTP miniature circuit breaker S273-K.
The 3AC V4 – devices must only be operated with three phases!
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after
switching off the power supply!
192-120101 N11 C3I11T11 November 2007
the device on again!
S015V4
S038V4
Three phase 3*400VAC/480VAC
80-528VAC / 50-60Hz
3Aeff
6Aeff
6A
10A
MTP miniature circuit breaker
Compax3 device description
S075V4
S150V4
S300V4
10Aeff
16Aeff
22Aeff
16A
20A
25A
D*
31