Compax3 device description
3.3.3.

Control voltage 24VDC / enable connector X4 C3S

26
PIN
Description
1
+24V (supply)
2
Gnd24 V
3
Enable_in
4
Enable_out_a
5
Enable_out_b
Control voltage 24VDC Compax3S and Compax3H
Controller type
Voltage range
Mains module
Fuse
Current drain of the device
Total current drain
Ripple
Requirement according to safe extra
low voltage (SELV)
Short-circuit proof
Hardware - enable (input X4/3 = 24VDC)
This input is used as safety interrupt for the power output stage.
Tolerance range: 18.0V - 33.6V / 720Ω
Safe standstill (X4/3=0V)
For implementation of the "Safe standstill" safety feature in accordance with the
"protection against unexpected start-up" described in EN1037. Observe
instructions in the corresponding section (see page 68) with the circuitry
examples!
The energy supply to the drive is reliably shut off, the motor has no torque.
A relay contact is located between X4/4 and X4/5 (normally closed contact)
Enable_out_a - Enable_out_b
Contact opened
Contact closed
Series connection of these contacts permits certain determination of whether all
drives are de-energized.
Relay contact data:
Switching voltage (AC/DC): 100mV -60V
Switching current: 10mA - 0.3A
Switching power: 1mW...7W
192-120101 N11 C3I11T11 November 2007
Positioning via digital I/Os
Line cross sections:
2
minimum: 0.25mm
maximum: 2.5mm
2
(AWG: 24 ... 12)
Compax3
21 - 27VDC
with switch-on current limitation, due to
capacitive load
MTP miniature circuit breaker or "delayed action
fuse", due to capacitive load
0.8A
0.8 A + Total load of the digital outputs +
current for the motor holding brake
0.5Vpp
yes
conditional (internally protected with 3.15AT)
Power output
stage is
activated
disabled