Braking Resistor / High Voltage Dc C3S Connector X2 - Parker Compax3S025V2 Operating Instructions Manual

Compax3 i11t11 positioning via digital i/os
Hide thumbs Also See for Compax3S025V2:
Table of Contents

Advertisement

Parker EME
Caution!
3.3.5.2
Power supply plug X1 for 3AC 230VAC/240VAC devices
PIN
Designation
1
L1
2
L2
3
L3
4
PE
Mains connection Compax3S1xxV2 3AC
Controller type
Supply voltage
Input current
Maximum fuse rating per device
(=short circuit rating)
The 3AC V2 – devices must only be operated with three phases!
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after
switching off the power supply!

Braking resistor / high voltage DC C3S connector X2

In this chapter you can read about:
Braking resistor / high voltage supply plug X2 for 1AC 230VAC/240VAC devices............................29
Braking resistor / high voltage supply plug X2 for 3AC 230VAC/240VAC devices............................30
Connection of a braking resistor ........................................................................................................30
The energy generated during braking operation is absorbed by the Compax3
storage capacity.
If this capacity is too small, the braking energy must be drained via a braking
resistor.
Braking resistor / high voltage supply plug X2 for 1AC
230VAC/240VAC devices
PIN
Designation
1
Reserved
2
- braking resistor (not short-circuit protected!)
3
PE
4
+ braking resistor (not short-circuit protected!)
5
Reserved
Braking operation Compax3S0xxV2 1AC
Controller type
Capacitance / storable energy
Minimum braking- resistance
Recommended nominal power rating
Maximum continuous current
192-120101 N11 C3I11T11 November 2007
Compax3 device description
S100V2
S150V2
Three phase 3* 230VAC/240VAC
80-253 VAC/50-60Hz
10Aeff
13Aeff
16 A (circuit breaker
20 A (circuit breaker K)
K)
S025V2
S063V2
560μF / 15Ws
1120μF / 30Ws
100Ω
56Ω
20 ... 60W
60 ... 180W
8A
15A
29