D7212GV3 | Program Entry Guide | 2.0
Use this prompt to determine whether these events
print at assigned printer.
P## Burglar Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Access Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## User Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Test Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Diag Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Auto Functions Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## RPS Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Relay Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Point Event
Default:
Refer to the program record sheet
Selection:
Yes or No
P## Usr Chng Evt
Default:
Refer to the program record sheet
Selection:
Yes or No
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Panel and Area Wide Parameters
2.6

RPS Parameters

Use these program items to enable remote
programming software (RPS) functions in the control
panel using the on-board phone connection or
Network Interface Module. Refer to Section 6.5 SDI
RPS Parameters on page 113 for more information
on these types of remote programming.
2.6.1

Uploading and Downloading Reports

If the control panel is programmed to send reports in
2
ModemIIIa
reporting format, when RPS contacts the
control panel and the passcode is incorrect, the
control panel sends an RPS Access Fail Report to
the central station receiver. RPS Access Fail also
occurs when the call is not terminated with either a
Good-bye or Reset-bye command.
RPS ACCESS OK is sent according to phone routing
when a Good-bye command is entered from RPS to
terminate the call.
When a Reset-bye is used to terminate the call, a
Remote Reset Report is sent to the central station
receiver, and an RPS ACCESS OK is placed into the
control panel's event log. Reports in the event log
that were not sent before the Reset-bye are never
sent to the central station receiver.
When RPS programming changes parameters, a
Parameters Changed Report is sent to the central
station receiver. If any programming changes are
made, perform a Reset-bye.
When RPS contacts the control panel, the RPS
passcode and DataLock code are verified. If the
control panel's passcode matches and the DataLock
code does not, the control panel still generates a
RPS Access OK Event; however, the session ends
immediately.
To prevent the control panel from answering the
telephone automatically, enter 0 in the Answer
Armed and Answer Disarmed prompts in this
section.
2.6.2

Log Threshold Reports

When the event log reaches the percentage
configured in Log % Full, the control panel attempts
to contact Unattended RPS as configured (by phone
or over Ethernet network).
If communication with RPS is unsuccessful, or if not
properly configured, the control panel generates Log
Threshold and Fail to Call RPS events.
EN | 26