Rps Parameters; Uploading And Downloading Reports; P## Fire Events; P## Burglar Event - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 2.0

P## Fire Events

Default:
Refer to the program record sheet
Selection:
Yes or No
Yes
All events in this group print at
assigned printer.
No
No events in this group print at
assigned printer.
Use this prompt to determine whether these events
print at assigned printer.

P## Burglar Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Access Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## User Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Test Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Diag Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Auto Functions Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## RPS Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Relay Event

Default:
Refer to the program record sheet
Selection:
Yes or No
Bosch Security Systems | 5/05 | F001U003636B
GV2MAIN

P## Point Event

Default:
Refer to the program record sheet
Selection:
Yes or No

P## Usr Chng Evt

Default:
Refer to the program record sheet
Selection:
Yes or No
2.7

RPS Parameters

Use these program items to enable remote
programming software (RPS) functions in the control
panel using the on-board phone connection. Two
other methods of remote programming are available
(external modem and LAN or WAN connection) using
RPS. Refer to Section 6.4 SDI RPS Parameters on page
121 for more information on these types of remote
programming.
2.7.1

Uploading and Downloading Reports

If the control panel is programmed to send reports in
modem format, when RPS contacts the control panel
and the passcode is incorrect, the control panel sends
an RPS Access Fail Report to the D6500/D6600. RPS
Access Fail also occurs when the call is not terminated
with either a Good-bye or Reset-bye command.
RPS ACCESS OK is sent according to phone routing
when a Good-bye command is entered from RPS to
terminate the call.
When a Reset-bye is used to terminate the call, a
Remote Reset Report is sent to the D6500/D6600, and
an RPS ACCESS OK is placed into the control panel's
event log. Reports in the event log that were not sent
before the Reset-bye are never sent to the
D6500/D6600.
When RPS programming changes parameters, a
Parameters Changed Report is sent to the
D6500/D6600. If any programming changes are made,
perform a Reset-bye.
When RPS contacts the control panel, the RPS
passcode and DataLock code are verified. If the
control panel's passcode matches and the DataLock
code does not, the control panel still generates a RPS
Access OK Event; however, the session ends
immediately.
To disable remote programming, enter Blank in both
Answer Armed
and
this section.
Answer Disarmed
prompts in
EN | 28

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv2

Table of Contents