Area Text - Bosch D7212GV3 Program Entry Manual

Table of Contents

Advertisement

D7212GV3 | Program Entry Guide | 2.0
You can use this prompt for a group of
account-wide keypads that only arm the
area to which they are assigned, even if
the user has a passcode with arming
authority rights in all areas.
CC# Scroll Lock
Default:
No
Selection:
Yes or No
Yes
Prevents the idle system status text
from scrolling automatically.
Requires user intervention to
advance.
No
Allows the idle system status text to
scroll automatically without user
intervention.
Use this parameter to enable a special non-scrolling
option for the idle system status display text on a
keypad. This keypad mode requires the user to press
PREV or NEXT on the keypad to unlock the display
and begin scrolling through the system status
displays.
CC# Menu Key Lock
Default:
No
Selection:
Yes or No
Yes
If set to Yes, the user is prompted to
enter a passcode after pressing the
Menu key on the keypad. The items
programmed in the Menu List for this
specific keypad are filtered by the
user's authority level. Only those
items in the menu list for which the
user has authority appear.
No
If set to No, when the user presses
the Menu key, all items that are
programmed in the Menu List for the
Command Center Address (Keypad
Address) appear, regardless of the
user's authority level.
Determines if the Menu Key, when pressed, requires
a passcode to access the functions.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Panel and Area Wide Parameters
If this parameter is set to Yes, users must
enter a passcode after pressing the Menu
key. When the passcode is validated,
only those functions for which the user
has authority appear in the list. If a
function in the Menu List is passcode
protected (refer to Keypad Functions in
Section 2.11.2 User Interface on page
54) the user does not need to enter the
passcode again.
CC# Abort Display
Default:
Selection:
Yes
No
This parameter enables or disables the ALARM NOT
SENT message when an alarm is aborted before
transmission occurs.
For SIA CP-01 Compliance
CC# Abort Display can be set to Yes or No.
CC# Cancel Display
Default:
Selection:
Yes
No
This parameter enables or disables the CANCEL
REPORT SENT display message when an alarm is
canceled after transmission occurs. To show this
message, Cancel Report must be set to Yes. Refer to
Cancel Report on page 31.
For SIA CP-01 Compliance
CC# Cancel Display can be set to Yes or No.
2.9.2

Area Text

Use this programming category to create custom Idle
Text displays for the keypads.
Yes
Yes or No
This keypad shows the Alarm
Aborted message for all aborted
alarms within its scope.
This keypad does not show the
Alarm Aborted message for all
aborted alarms within its scope.
Yes
Yes or No
This keypad shows the Cancel
Report Sent message for all canceled
alarms within its scope.
This keypad does not show the
Cancel Report Sent message for all
canceled alarms within its scope.
EN | 50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents