D7212GV3 | Program Entry Guide | 2.0
Table 17: Event Descriptions, Priorities, and
Numbers, continued
Event Description
Parameters Changed
RPS Access OK
RPS Access Fail
Remote Reset
Program Access OK
Program Access Fail
Service Start
Service End
Fire Walk Start
Fire Walk End
Walk Test Start
Walk Test End
Extra Point
Send Point Text
RF Low Battery
RF Battery Restore
Date Changed
Time Changed
Delete User
User Code Change
Area Watch
1
Card Assigned
1
Change Level
1
Access Granted
1
No Entry
1
Door Left Open
1
Cycle Door
1
Door Unlocked
1
Door Secure
1
Door Request
1
Door Locked
User Alarm COMMAND 7
User Alarm COMMAND 9
1
This event is not transmitted for the D7212GV3. Use
only the default setting.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Panel and Area Wide Parameters
2.4
AC Fail Time
Event
Event
Priority
Number
008
054
Program the amount of time that AC power must be
008
064
off before the control panel responds to the AC
008
065
failure. The response to restoral of AC power is
008
079
delayed for the same amount of time. The control
n/a
n/a
panel always monitors AC. The response to this
n/a
n/a
prompt is the actuation of the relay programmed in
008
029
the Panel-Wide Relays prompt AC Failure (refer to
008
030
Section 2.12.2 Panel-Wide Relays on page 72) and
008
036
the AC Fail report enabled by the AC Fail/Restoral
008
037
Report prompt. Local annunciation of an AC failure is
008
038
controlled by the AC Fail Display prompt.
008
039
008
023
Resend AC Fail
n/a
n/a
006
093
006
094
008
059
008
060
008
090
008
056
008
042
008
110
007
061
008
003
008
115
008
116
This prompt controls the repeated transmission of the
008
112
AC Failure report to the central station while the fault
008
113
persists. AC Fail/Restoral Report must be set to
008
114
Yes, and AC Tag Along must be set to No for this
008
117
feature to work.
008
145
002
005
002
006
AC Fail Display
Program the length of time the AC power must be off
before the message SERVC AC FAIL shows on the
keypads. The response to restoral of AC power is
delayed for the same amount of time.

Power Supervision

Default:
1:00
Selection:
0:01 to 90:00
Default:
No Response
Selection:
No Response, 6 hrs, 12 Hrs
No
Only send the AC Fail report upon
Response
failure.
6 hr
Send AC Fail report upon failure and
every 6 hours after this while the
failure persists.
12 hr
Send AC Fail report upon failure and
every 12 hours after this while the
failure persists.
To eliminate AC Reporting, AC Tag
Along and AC Fail/Restoral Report
must be programmed as No.
Default:
60 sec
Selection:
10 to 300 sec (in 5-sec
increments)
EN | 23