Sia False Alarm Reduction Installations: Quick Reference - DSC HS2128 Reference Manual

Powerseries neo alarm controller
Hide thumbs Also See for HS2128:
Table of Contents

Advertisement

24 h check in transmission shall be enabled
l
Open/Closing acknowledgement enabled.(Not Police Station)
l
The Installation shall use the internal dialer (DACT) alone or in conjunction with Models TL2803G(R) IP/3G Interface, 3G2080(R) 3G Interface or TL280(R) IP
l
Interface, which communicates over Cellular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV receiver
UL Home Health Care Signaling Equipment
There must be at least two keypads, one of either one of the compatible keypads models HS2LED, HS2LCD(P), HS2ICN(P), HS2LCDRF(P)9, HS2ICNRF
l
(P)9 and HS2TCHP
Each system shall be programmed to activate an audible Trouble signal within 90 seconds upon loss of microprocessor memory
l
The HS2TCHP shall be used along with another compatible model keypad in order to provide audible supervision for homehealth care or medical install-
l
ations.
ULC Central Station Fire and Burglary Monitoring Installations
For installation requirements, levels of security, communication modules and configurations (Refer to the ULC Installation Information Sheet, DSC
l
#29002157)
Use a CSA/cUL approved transformer (hardwired connections required for Fire Monitoring)
l
All tamper circuits may be connected to the same zone
l
HS2TCHP touch screen keypad is for supplementary use only with ULC Commercial Fire Monitoring
l
Programming
The notes in the programming sections of the PowerSeries Neo Reference Manual describing the system configurations for UL/ULC listed installations shall be imple-
mented.
Control of the Protected Premises
In order to have a UL certificated system, the protected area shall be under the responsibility of one ownership and management (i.e., one business under one name).
This may be a group of buildings attached or unattached with different addresses but under the responsibility of someone having mutual interest. The person of mutual
interest is not the alarm-installing company.
Note: This does not apply to strip mall applications where each independent business must have their own separate alarm system.
e.g.,1: A commercial partitioned system that has an office and a warehouse area in a building where each area can be armed or disarmed independently. e.g.,2: A res-
idential system partitioned so that the garage area is armed separately from the house.
Each of the above examples is under the sole responsibility of a single owner. The bell and DACT power supply must be in a protected area including partitioned sys-
tems. The bell and DACT power supply must be located where it can be heard by the person or persons responsible for maintaining the security system during the
daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and the local power supply must be protected in one of the following ways:
The control unit and audible alarm device must be in a protected area which is armed 24 hours a day.
l
Each partition must arm the area protecting the control unit and the audible alarm device power supply. This may require duplicate protection armed by each
l
partition. Access to this protected area, without causing an alarm, will require that all partitions be disarmed.
In all cases described above, the protected area for the control unit must be programmed as not-bypassable.
l
Casual Users
The installer should caution the user not to give system information (e.g., codes, bypass methods, etc.) to casual users (e.g., service people) and to only give out
One-Time Use codes.
User Information
The installer should advise the user and note in the User's Manual:
Service organization name and telephone number
l
The programmed exit and entry time
l
Instructions to test system weekly
l
Note that the installer code cannot arm or disarm the system
l
4.1

SIA False Alarm Reduction Installations: Quick Reference

Minimum required system consists of one Control unit model HS2128 or HS2064 or HS2032 or HS2016-4 and any one of
the compatible listed keypads: HS2LCDRF9, HS2LCDRFP9, HS2ICNRF9, HS2ICNRFP9, HS2LCD, HS2LCDP, HS2ICN,