DSC HS2128 Reference Manual page 98

Powerseries neo alarm controller
Hide thumbs Also See for HS2128:
Table of Contents

Advertisement

Section 6: Programming
[015] System Option 3
1 – [F] Key Enabled
ON: Pressing and holding the [F] key for 2 seconds triggers a Fire alarm.
OFF: The [F] key does not sound or report an alarm when pressed.
Note: Use only for residential fire installations.
2 – [P] Key Enabled
ON: When a valid [P] key alarm is generated, the keypad buzzer emits a series of 3 beeps to acknowledge the alarm and the
siren sounds for the length of bell timeout.
OFF: When a valid [P] key alarm is generated, the keypad buzzer and the siren are silent, but the alarm is still transmitted (if
programmed).
Note: Fire, Medical, and Panic key transmissions follow the partition 1 alarm/restore call direction options (Fire, Medical, and
Panic key). The Fire, Medical, Panic keys operate even if keypad blanking and keypad lockout are active.
3 – Quick Exit
ON: When the system is armed, users may enter the [*][0] command to temporarily bypass a single Delay 1 or Delay 2 zone
to exit the premises. Only one delay zone may be activated. Activity on another delay zone initiates the appropriate alarm
sequence. If the delay zone is still open two minutes after the [*][0] command is entered, entry delay is initiated. If armed in
the Stay mode, the automatic bypass on Stay/Away zones remains.
OFF: When the system is armed, users can not perform a quick exit using [*][0].
4 – Quick Arming /Function Key
ON: [*][0] arming and Stay/Away function keys may be used to arm the system without the entry of a valid access code.
OFF: [*][0] arming is not permitted. All arming functions require the entry of an access code to activate (including Stay/Away
keys).
5 – Not Used
6 – Master Code Not User Changeable
ON: The master code (access code 01) may not be changed by the user and may only be programmed in Installer Pro-
gramming.
OFF: The master code may be programmed by the user using the [*][5][Master Code] command. The master code may also
be programmed in Installer Programming.
7 – Telephone Line Monitor Enable
ON: The TLM function is active and the system indicates a trouble condition when using the [*][2] View Trouble Conditions
command.
OFF: The TLM function is deactivated and telephone line troubles are not indicated by the system.
NA
Note: Must be ON for UL/ULC listed installations.
8 – Telephone Line Monitor Audible When Armed
ON: When the system is disarmed, a telephone line monitor trouble generates a trouble indication as described above. If the
system is armed, a telephone line monitor trouble generates an audible alarm on the siren for the duration programmed for
bell timeout or until an access code is entered to disarm.
OFF: Telephone line troubles generate a trouble indication, the Trouble LED illuminates, and the keypad buzzer beeps until
a key is pressed.
- 98 -