DSC HS2128 Reference Manual page 97

Powerseries neo alarm controller
Hide thumbs Also See for HS2128:
Table of Contents

Advertisement

Section 6: Programming
OFF: The event buffer continues to log events to the buffer even after the event has gone into swinger shutdown.
8 – Temporal Three Fire Signaling
ON: All fire bells sound in the temporal three pattern. Cadence is as follows: (500ms ON, 500ms OFF, 500ms ON, 500ms
OFF, 500ms ON, 1.5 sec. OFF).
OFF: All fire bells will sound with the standard 1 second on/1 second off fire bell cadence.
Note: Must be on for UL/ULC installations.
[014] System Option 2
1 – Bell Squawk
ON: The siren emits a single squawk when armed in any manner, including Auto-arm, and a double squawk when disarmed.
When the system is disarmed, the siren emits a series of three squawk pairs to indicate alarms in memory.
OFF: The siren does not squawk when arming or disarming.
NA
Note: For UL/ULC, must be enabled if wireless keys are used with the alarm system.
2 – Bell Squawk on Auto-Arm
ON: The siren squawks once every 10 seconds during the auto-arm pre-alert time.
OFF: The siren does not squawk during auto-arm pre-alert.
3 – Bell Squawk On Exit
ON: The siren squawks once per second during exit delay, changing to 3 squawks per second for the final 10 seconds.
OFF: The siren does not squawk for exit delay conditions.
4 – Bell Squawk On Entry
ON: The siren pulses with the same timing as the keypad buzzer during entry delay, changing to 3 squawks per second for
the final 10 seconds.
OFF: The siren does not activate during entry delay.
5 – Bell Squawk On Trouble
ON: When a trouble condition exists on the system, the siren squawks 2 times every 10 seconds (as per the keypad buzzer).
The siren is silenced when the keypad beeps are silenced (any key pressed on keypad).
OFF: The siren does not activate with a trouble condition.
6 – Not Used
7 – Exit Delay Termination
ON: The exit delay is reduced to 5 seconds once a Delay 1 zone is restored. Force-Arm Delay 1 type zones also end the exit
delay.
OFF: The exit delay timer continues to count even after the delay zone is restored.
All audible options associated with the exit delay function are silenced until the time programmed for the exit delay has
elapsed.
8 – Fire Bell Continues
ON: For all Fire type alarms, the siren sounds until an access code is entered to silence the alarm or disarm the system
regardless of the time programmed for bell timeout.
OFF: For all Fire type alarms, the siren sounds for the length of Bell Timeout or until an access code is entered.
ULC
Note: Must be disabled for ULC installations.
- 97 -