DSC HS2128 Reference Manual page 47

Powerseries neo alarm controller
Hide thumbs Also See for HS2128:
Table of Contents

Advertisement

Program Bypass Group
To program a bypass group, bypass all desired zones then select Bypass Options > Program Bypass Group. The selected
zones are saved to the bypass group. When finished, press [#] to exit.
In order to program a bypass group, a master or supervisor code with access to the appropriate partition must be used.
Bypass Recall
Press [*] while in this menu to bypass the same group of zones that were bypassed the last time the partition was armed.
Clear Bypasses
Press [*] to clear all bypasses.
Shortcuts from the [*][1] base menu:
991 = bypass group
995 = program group 1
998 = bypass open zones
999 = bypass recall
000 = clear group
When The Alarm System is Armed
When the system is armed, pressing [*][1] toggles between stay, away or night arming. If a night zone is on the system, press-
ing [*][1] either prompts the user for an access code if required, or sounds an acknowledgment tone and changes the arming
mode.
Note: If section [022], Option 5 [Stay/Away Toggle] is on, the system does not change from Away to Stay mode.
The zone attribute for zone bypassing must be enabled (see section [002] Zone Attributes, Option 04).
Holdup zones should not be part of bypass groups.
A zone that is manually bypassed via [*][1] will bypass the alarm, fault, and tamper conditions when DEOL is used.
If a 24-hour zone is bypassed, ensure that the zone is restored or disabled before removing the bypass.
5.7.2 Troubleshooting
LCD programmable-message keypad:
Press [*][2] followed by access code if required to view a trouble condition
l
The trouble light flashes and the LCD displays the first trouble condition
l
Use the arrow keys to scroll through all trouble conditions present on the system
l
Note: When additional information is available for a specific trouble condition, a [*] is displayed. Press the [*] key to view the
additional information.
LED and ICON keypads:
Press [*][2] to view a trouble condition
l
The trouble light flashes
l
Refer to the trouble summary list below to determine the trouble condition(s) present on the system
l
5.7.3 [*][2] Trouble Display
This feature is used to view system troubles. If a trouble is present, the keypad Trouble indicator illuminates and an audible
indication is emitted (two short beeps every 10 seconds, except while in AC failure). Silence the audible indicator by press-
ing [#].
Section 5: System Operation