Each day programmed in the counter represents one day plus the time it takes for the partition to reach midnight. To disable
this feature, program 000 in section [377]>[002] option 5.
[381] Communicator Option 2
1 – Keypad Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad emits a series of 8 beeps to confirm to the occupant that the code was sent and received. Ringback occurs for each
successfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad does not sound ringback.
2 – Bell Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
emits a series of 8 squawks to confirm to the occupant that the code was sent and received. Ringback occurs for each suc-
cessfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
does not sound ringback.
4 – Closing Confirmation Enabled/Disabled
ON: When a Closing reporting code is successfully transmitted to a programmed telephone number, the keypad emits a
series of 8 beeps to confirm to the occupant that the Closing Code was sent and received.
OFF: No keypad ringback is generated when a Closing reporting code is successfully transmitted.
8 – Communications Priority Enabled/Disabled
ON: Events follow the priority level indicated in ULC-S559 standard.
Concurrent event communications are prioritized in the following order (highest to lowest priority):
1. Fire Alarms
2. CO Alarm
3. Fire Supervisories
4. Fire Trouble
5. Monitoring (Medical, Panic or Security)
6. All others such as restorals for fire alarms, supervisories, troubles and monitoring.
7. FTC'ed events
OFF: Events are communicated in the order they occur.
ULC
Note: Must be ON for ULC commercial fire monitoring listed installations.
[382] Communicator Option 3
1 – Not Used
2 – Walk Test Communications
ON: Zone alarms that occur during Walk Test are communicated if programmed to do so.
OFF: Zone alarms during Walk Test are not communicated. FMP key alarms are still communicated.
4 – Call Waiting Cancel
ON: The call waiting cancel string (See "[304] Call Waiting Cancel String" on page 113) is used on the first attempt to dial
each phone number. It is not used on any further dialing attempts.
OFF: The call waiting cancel string is not dialed.
Section 6: Programming
- 125 -