Section 6: Programming
[004] – Periodic Test Transmission Time of Day
Enter a 4-digit time using the 24-hour clock format (HH:MM).
Valid entries are from 00 to 23 for the hours (HH) and 00 to 59 for the minutes (MM).
To disable the test transmission time of day, enter [9999] in this section.
Note: This time should not be set for the same time as Day Light Savings time.
[011] – Maximum Dialing Attempts
This section is used to program the number of dialing attempts made to each telephone number when communicating. Valid
entries are 002-005.
NA
Note: For UL/ULC listed installations, this value must be set to 005.
[012] – Delay Between PSTN Attempts
This programmable timer adds a delay before the next call is attempted over PSTN. Valid entries are 000-255, with a default
of 3 seconds (making a total of 8 seconds: 3-second delay + standard 5-second dial tone search).
[013] – Delay Between Force Attempts
This programming option is used to set the length of time the alarm system waits between the first dialing attempt and the
force dial attempt.
Valid Entries are 001-255 seconds. Default is 020.
[014] – Post Dial Wait for Handshake
This option is used to program the length of time the communicator waits for a valid initial handshake from the receiver after
dialing the programmed telephone number. Valid entries are 001 to 255 seconds.
UL
Note: Maximum 45 seconds for UL installations.
[015] – T-Link Wait for Ack
This option is used to program the length of time the communicator waits for an acknowledge after transmitting via IP/GS.
Valid entries are 001 to 255. Default is 60 seconds.
[016] –IP/Cellular Fault Check Timer
This section is used to program the number of poll commands sent without valid poll responses before the alarm system gen-
erates a trouble condition. The checks occur at 3-second intervals.
Valid entries are 003-255 for trouble annunciation and transmission.
The trouble restore is not delayed.
[380] Communicator Option 1
1 – Communications Enabled/Disabled
ON: (Default) The system communicator is enabled and all events with reporting codes are reported to the monitoring sta-
tion. Refer to the Telephone Number, Reporting Code and Call Direction programming sections.
OFF: The system communicator is disabled and no events are reported to the monitoring station.
Note: Disabling the communicator clears all FTC troubles.
2 – Restore On Bell Timeout
ON: Zone restore reporting codes are not transmitted until the zone has been restored and the bell timeout has expired. If the
zone is not restored when the bell cut-off time expires, the restore is transmitted when the zone physically restores or when
the system is disarmed.
Note: 24-hour zones will not restore until the zone is physically restored