H02 PAM Trouble (Single-phase only)
1.
Error Detection Method
Error is detected by over-voltage and overcurrent of DC side.
2.
Error Diagnosis
1 Power
1-1
supply*
1-2
1-3
2 PC board
2-1
wiring
2-2
2-3
*
Check not only in the outdoor unit stop mode but in the drive mode.
5
Not satisfied with + 10% rated supply voltage
Extreme voltage fluctuations
Extreme distortion of voltage waveform
Loose electrical wire connection
Is HIC PC board connector (CN-PAM) poorly connected or
opened with wire?
Replace HIC PC board.
5-38
Yes
Check power supply
No
1-2
Yes
Check power supply
No
1-3
Yes
Check power supply
No
2-1
Yes
Correct connection
No
2-2
Correct connection
Yes
or wiring
No
2-3

Advertisement