Panasonic S-36PU1E5A Technical Data & Service Manual page 289

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

K1 Type
Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2).
* If multiple indoor units are used, also refer to section "System Control" for K1 type.
The indoor and outdoor unit control PCB utilizes a semiconductor memory element (EEPROM).
The settings required for operation were made at the time of shipment.
Only the correct combinations of indoor and outdoor units can be used.
Test Run Procedure
Check the combination (wiring) of indoor and outdoor units.
YES
Turn ON the indoor
and outdoor power
(Automatic Address Setting)
Recheck the items to check before the test run.
Is system "single-type"?
(1 indoor unit is connected
to 1 outdoor unit)
NO
Are multiple outdoor units used?
NO
Turn ON the indoor and outdoor power.
(Automatic Address Setting)
Set the indoor unit control switch to "TEST".
Can operation
be started?
YES
Slide the indoor unit control
switch back to "ON".
See section "Test Run" for K1 type.
1-279
See section "Items to Check
Before the Test Run" for K1 type.
See section "System Control"
for K1 type.
(See section "Basic wiring
diagram 2" for K1 type.)
In case of group control
Confirm wiring is done in
YES
accordance with "Basic
wiring diagram 2" for K1 type.
(See section "Setting the outdoor unit
system addresses" for K1 type to "Indoor
unit address setting".)
How to Set Automatic Address
Set the automatic
address setting
from outside unit.
See section "Test Run" for K1 type.
See section "Table of Self-Diagnostic
Functions and Corrections (K1 type)" .
Refer to "Table of Self-Diagnostic
NO
Functions" to check the system.
In addition, refer to "System control"
for K1 type and correct any items
that need to be corrected.
Note: Check the indoor side drainage.
1

Advertisement

Table of Contents
loading

Table of Contents