Panasonic S-36PU1E5A Technical Data & Service Manual page 553

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

F07 Intermediate Temperature Sensor (C2) in Heat Exchanger Trouble
1.
Error Detection Method
It is judged an error when open circuit or short circuit.
2.
Error Diagnosis
1 Sensor
1-1
Sensor connector is connected to PC board properly.
1-2
Resistance between sockets is infinity or 0 ohm.
2 PC board
2-1
Replace PC board because of outdoor control PC board failure.
5-31
Yes
1-2
No
Reconnect and check
Yes
Replace sensor
No
2-1
5

Advertisement

Table of Contents
loading

Table of Contents