Panasonic S-36PU1E5A Technical Data & Service Manual page 200

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

1
1-2. Dimensional Data
(A) Indoor Units: S-36PU1E5A / S-45PU1E5A / S-50PU1E5A / S-60PU1E5A / S-71PU1E5A
840
Less than 35
7
8
Raise dimension of drain tube
The length of the suspension bolts
should be selected so that there is
a gap of 30 mm or more below the
lower surface of the ceiling (18 mm
or more below the lower surface of
the main unit), as shown in the
figure at right. If the suspension
bolt is too long, it will contact
the ceiling panel and the unit
cannot be installed.
1
Air intake
2
Discharge outlet
3
Refrigerant tubing (liquid tube) 36-50 type ø6.35 (flared), 60 • 71 type ø9.52 (flared)
4
Refrigerant tubing (gas tube) 36-50 type ø12.7 (flared), 60 • 71 type ø15.88 (flared)
5
Drain tube connection port VP25 (outer dia. ø32)
6
Power supply port
7
Discharge duct connection port (ø150)
8
Vaporization-type humidifier (optional) installation area
9
Suspension bolt hole (4-12×30 elongated hole)
10
Fresh air intake duct connection port (ø100) *
* Necessary to provide optional air intake kit.
<Filter dimension>
520 x 520 x 16
9
480
2
Less than 35
Less than 300
2
1
X
860~910
(Ceiling opening dimensions)
786
(Suspension bolt pitch)
324
3
5
4
840
271
50
145
7
6
950
514
2
2
1-190
Z
82
10
7
2
480
8
7
View X
115
Detailed view Y
80
Detailed view Z
unit: mm
Y
160