System address
No.
0 Automatic address
(Setting at shipment = "0")
1 (If outdoor unit is No. 1)
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30 (If outdoor unit is No. 30)
Case 1
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
Be sure to use a jig for short-circuiting.
Automatic address setting from the outdoor unit (K1 type)
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the AUTO ADD (CN041) pin.
The compressor operates when the power is turned ON at a different outdoor unit.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system.
Short-circuit the AUTO ADD (CN041) pin.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
System address
System address
10s digit
(2P DIP switch)
(Rotary switch)
Both OFF
ON
ON
1
2
OFF
Both OFF
ON
ON
1
2
OFF
Both OFF
ON
ON
1
2
OFF
10s digit ON
ON
ON
1
2
OFF
20s digit ON
ON
ON
1
2
OFF
10s digit and 20s
digit ON
ON
ON
1
2
OFF
<Approximately 4 – 5 minutes are required.>
1-298
1s place
"0" setting
"1" setting
"2" setting
"1" setting
"1" setting
"0" setting