Panasonic S-36PU1E5A Technical Data & Service Manual page 304

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

1
K1 Type (for Link Wiring)
Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2).
If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to
be identified.
At the same time, indicate the indoor-outdoor unit combination number in a location where it can be checked
easily (near the indoor unit nameplates). (This number will be required for subsequent maintenance.
Refer to section "Checking indoor unit addresses" and "Indicating (marking) the indoor and outdoor unit
combination number" for K1 Type (for Link Wiring).)
Request that the customer be present when the test run is performed. At this time, explain the Operating Instructions
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the 220 – 240 V AC wiring is not connected to the inter-unit control wiring connector terminal.
If 220 – 240 V AC is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor and
outdoor units) will blow in order to protect the PCB.
Correct the wiring connections, then disconnect the 2P connectors (indoor: blue, OC) (outdoor: blue, serial 1)
that are connected to the PCB, and replace them with 2P connectors (indoor: brown, EMG) (outdoor: brown,
serial 2).
If operation is still not possible after changing the brown connectors, cut off the jumper (outdoor unit : JP007) or
the varistor (indoor unit) on the PCB.
(Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
2 HP
2P connector (blue)
3 HP
Varistor (black)
VA002
Fuse (0.5A)
CHK (2P plug)
ON
SW103
OFF
TEST
2P connector (brown)
Fuse (0.5A)
2P connector (blue)
2P connector
(brown)
TEST
ON
SW103
OFF
Varistor (black)
VA002
CHK (2P plug)
Outdoor unit control PCB
HIC
Temperature
sensor
Up side
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
Bottom
side
1-294
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
RC-P(CN032,RED)
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
SILENT MODE
(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)