Panasonic S-45PU1E5 Technical Data & Service Manual

Hide thumbs

Advertisement

Table of Contents
TECHNICAL DATA & SERVICE MANUAL
R410A Models
Model No.
Indoor Units
Indoor
Type
Units Type
U1
4-Way Cassette
4-Way Cassette
Y1
60×60
T1
Ceiling
T2
Ceiling
K1
Wall Mounted
Low Silhouette
F1
Ducted
N1
Ducted
Outdoor Units
Type
Outdoor Units Type
Single Split (1-phase)
PE1
Single Split (3-phase)
Single Split (1-phase)
PEY1
Single Split (3-phase)
85464849311007
Indoor Unit
4-Way Cassette
4-Way Cassette 60×60
Ceiling
Wall Mounted
Low Silhouette Ducted
Ducted
36
45
S-36PU1E5
S-45PU1E5
S-50PU1E5
S-36PY1E5
S-45PY1E5
S-36PT1E5
S-45PT1E5
S-36PT2E5
S-45PT2E5
S-36PK1E5
S-45PK1E5
S-50PK1E5
S-36PF1E5
S-45PF1E5
S-36PN1E5
S-45PN1E5
S-50PN1E5
50
U-50PE1E5
50
60
S-60PU1E5
S-71PU1E5 S-100PU1E5 S-125PU1E5 S-140PU1E5
S-50PY1E5
S-50PT1E5
S-60PT1E5
S-71PT1E5 S-100PT1E5 S-125PT1E5 S-140PT1E5
S-50PT2E5
S-60PT2E5
S-71PT2E5 S-100PT2E5 S-125PT2E5 S-140PT2E5
S-60PK1E5
S-71PK1E5
S-50PF1E5
S-60PF1E5
S-71PF1E5 S-100PF1E5 S-125PF1E5 S-140PF1E5
S-60PN1E5
S-71PN1E5 S-100PN1E5 S-125PN1E5 S-140PN1E5
60
71
U-60PE1E5
U-71PE1E5
U-71PE1E8
U-60PEY1E5
U-71PEY1E5 U-100PEY1E5 U-125PEY1E5
Order No. SBPAC1301005CE
Outdoor Unit
71
100
100
U-100PE1E5
U-125PE1E5
U-100PE1E8
U-125PE1E8
U-100PEY1E8 U-125PEY1E8
REFERENCE NO.
Order No. SM830211-11CE
125
140
125
140
U-140PE1E5
U-140PE1E8
U-140PEY1E8
SM830211-07

Advertisement

Table of Contents
loading

  Summary of Contents for Panasonic S-45PU1E5

  • Page 1 4-Way Cassette 60×60 Ceiling Wall Mounted Low Silhouette Ducted Ducted R410A Models Model No. Indoor Units Indoor Type Units Type 4-Way Cassette S-36PU1E5 S-45PU1E5 S-50PU1E5 S-60PU1E5 S-71PU1E5 S-100PU1E5 S-125PU1E5 S-140PU1E5 4-Way Cassette S-36PY1E5 S-45PY1E5 S-50PY1E5 – – – – –...
  • Page 2 When Transporting IMPORTANT! Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees This air conditioner must be installed by the sales dealer when lifting to reduce strain on your back. Sharp edges or installer.
  • Page 3 • Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts. Handle liquid refrigerant carefully as it may cause frostbite. When Servicing • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
  • Page 4: Check Of Density Limit

    Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
  • Page 5: Important Information Regarding The Refrigerant Used

    IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R410A value: 1975 GWP = global warming potential Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.
  • Page 6: Combination Of Indoor And Outdoor Units

    Combination of Indoor and Outdoor Units Single-phase S-36PU1E5 x2 S-45PU1E5 x3 S-50PU1E5 S-60PU1E5 S-71PU1E5 S-100PU1E5 S-125PU1E5 S-140PU1E5 U-71PE1E5 U-125PE1E5 U-50PE1E5 U-60PE1E5 U-71PE1E5 U-100PE1E5 U-125PE1E5 U-140PE1E5 S-36PU1E5 x3 S-50PU1E5 x2 S-60PU1E5 x2 S-71PU1E5 x2 U-100PE1E5 U-100PE1E5 U-125PE1E5 U-140PE1E5 S-36PU1E5 x4 S-50PU1E5 x3...
  • Page 7 Combination of Indoor and Outdoor Units 3-phase S-36PU1E5 x2 S-45PU1E5 x3 S-50PU1E5 x2 S-60PU1E5 x2 S-71PU1E5 S-100PU1E5 S-125PU1E5 S-140PU1E5 U-71PE1E8 U-125PE1E8 U-100PE1E8 U-125PE1E8 U-71PE1E8 U-100PE1E8 U-125PE1E8 U-140PE1E8 S-36PU1E5 x3 S-50PU1E5 x3 S-71PU1E5 x2 U-100PE1E8 U-140PE1E8 U-140PE1E8 S-36PU1E5 x4 U-125PE1E8 S-36PY1E5 x2...
  • Page 8 Combination of Indoor and Outdoor Units PEY1 Single-phase S-36PU1E5 x2 S-50PU1E5 x2 S-60PU1E5 S-71PU1E5 S-100PU1E5 S-125PU1E5 U-60PEY1E5 U-71PEY1E5 U-100PEY1E5 U-125PEY1E5 U-71PEY1E5 U-100PEY1E5 P165 P166 P167 P169 P170 P171 S-60PU1E5 x2 U-125PEY1E5 P168 S-36PY1E5 x2 S-50PY1E5 x2 U-71PEY1E5 U-100PEY1E5 P178 P179 S-36PT1E5 x2 S-50PT1E5 x2 S-60PT1E5...
  • Page 9: Table Of Contents

    —— CONTENTS —— Section 1. SPECIFICATIONS....................1-1 1-1. Unit Specifications ........................1-2. Dimensional Data ........................ 1-241 1-3. Refrigerant Flow Diagram ....................1-255 1-4. Operating Range ......................... 1-258 1-5. Capacity Correction Graph According to Temperature Condition ........1-259 1-6. Noise Criterion Curves ......................
  • Page 10 Section 6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL ........6-1. Overview ..........................6-2. Functions..........................6-3. Normal Display Operations and Functions ................6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ..6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ....6-6.
  • Page 11: Dimensional Data

    1. SPECIFICATIONS 1-1. Unit Specifications....................1. 4-Way Cassette Type (U1) ....................... 2. 4-Way Cassette 60×60 Type (Y1) ....................1-28 3. Ceiling Type (T1) ..........................1-41 4. Ceiling Type (T2) ..........................1-67 5. Wall Mounted Type (K1) ........................1-93 6. Low Silhouette Ducted Type (F1) .....................
  • Page 12 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×2 / U-71PE1E5 INDOOR MODEL S-36PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 13 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×3 / U-100PE1E5 INDOOR MODEL S-36PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 14 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×4 / U-125PE1E5 INDOOR MODEL S-36PU1E5×4 PANEL MODEL CZ-KPU2×4 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 15 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-45PU1E5×3 / U-125PE1E5 INDOOR MODEL S-45PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5...
  • Page 16 Single-Type 1-1. Unit Specifications 1. 4-Way Cassette Type S-50PU1E5 / U-50PE1E5 INDOOR MODEL S-50PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100 5100...
  • Page 17 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-50PU1E5×2 / U-100PE1E5 INDOOR MODEL S-50PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 18 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-50PU1E5×3 / U-140PE1E5 INDOOR MODEL S-50PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 19 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-60PU1E5 / U-60PE1E5 INDOOR MODEL S-60PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500...
  • Page 20 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-60PU1E5×2 / U-125PE1E5 INDOOR MODEL S-60PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 21 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-71PU1E5 / U-71PE1E5 INDOOR MODEL S-71PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 22: Unit Specifi Cations

    Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-71PU1E5×2 / U-140PE1E5 INDOOR MODEL S-71PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 23 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-100PU1E5 / U-100PE1E5 INDOOR MODEL S-100PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY...
  • Page 24 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-125PU1E5 / U-125PE1E5 INDOOR MODEL S-125PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY...
  • Page 25 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-140PU1E5 / U-140PE1E5 INDOOR MODEL S-140PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY...
  • Page 26 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×2 / U-71PE1E8 INDOOR MODEL S-36PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 27 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×3 / U-100PE1E8 INDOOR MODEL S-36PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 28 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-36PU1E5×4 / U-125PE1E8 INDOOR MODEL S-36PU1E5×4 PANEL MODEL CZ-KPU2×4 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 29 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-45PU1E5×3 / U-125PE1E8 INDOOR MODEL S-45PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5...
  • Page 30 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-50PU1E5×2 / U-100PE1E8 INDOOR MODEL S-50PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 31 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-50PU1E5×3 / U-140PE1E8 INDOOR MODEL S-50PU1E5×3 PANEL MODEL CZ-KPU2×3 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 32 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-60PU1E5×2 / U-125PE1E8 INDOOR MODEL S-60PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 33 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-71PU1E5 / U-71PE1E8 INDOOR MODEL S-71PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 34 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-71PU1E5×2 / U-140PE1E8 INDOOR MODEL S-71PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 35 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-100PU1E5 / U-100PE1E8 INDOOR MODEL S-100PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY...
  • Page 36 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-125PU1E5 / U-125PE1E8 INDOOR MODEL S-125PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY...
  • Page 37 Single-Type 1-1. Unit Specifi cations 1. 4-Way Cassette Type S-140PU1E5 / U-140PE1E8 INDOOR MODEL S-140PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY...
  • Page 38 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×2 / U-71PE1E5 INDOOR MODEL S-36PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h...
  • Page 39 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×3 / U-100PE1E5 INDOOR MODEL S-36PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 40 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×4 / U-125PE1E5 INDOOR MODEL S-36PY1E5×4 PANEL MODEL CZ-KPY2×4 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 41 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-45PY1E5×3 / U-125PE1E5 INDOOR MODEL S-45PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 42 Single-Type 1-1. Unit Specifications 2. 4-Way Cassette 60×60 Type S-50PY1E5 / U-50PE1E5 INDOOR MODEL S-50PY1E5 PANEL MODEL CZ-KPY2 OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100...
  • Page 43 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-50PY1E5×2 / U-100PE1E5 INDOOR MODEL S-50PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 44 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-50PY1E5×3 / U-140PE1E5 INDOOR MODEL S-50PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 45 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×2 / U-71PE1E8 INDOOR MODEL S-36PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h...
  • Page 46 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×3 / U-100PE1E8 INDOOR MODEL S-36PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 47 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-36PY1E5×4 / U-125PE1E8 INDOOR MODEL S-36PY1E5×4 PANEL MODEL CZ-KPY2×4 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 48 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-45PY1E5×3 / U-125PE1E8 INDOOR MODEL S-45PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 49 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-50PY1E5×2 / U-100PE1E8 INDOOR MODEL S-50PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 50 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 2. 4-Way Cassette 60×60 Type S-50PY1E5×3 / U-140PE1E8 INDOOR MODEL S-50PY1E5×3 PANEL MODEL CZ-KPY2×3 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 51 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×2 / U-71PE1E5 INDOOR MODEL S-36PT1E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 52 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×3 / U-100PE1E5 INDOOR MODEL S-36PT1E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 53 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×4 / U-125PE1E5 INDOOR MODEL S-36PT1E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 54 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-45PT1E5×3 / U-125PE1E5 INDOOR MODEL S-45PT1E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 55 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-50PT1E5 / U-50PE1E5 INDOOR MODEL S-50PT1E5 PANEL MODEL OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100 5100...
  • Page 56 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-50PT1E5×2 / U-100PE1E5 INDOOR MODEL S-50PT1E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 57 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-50PT1E5×3 / U-140PE1E5 INDOOR MODEL S-50PT1E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 58 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-60PT1E5 / U-60PE1E5 INDOOR MODEL S-60PT1E5 PANEL MODEL OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 8500...
  • Page 59 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-60PT1E5×2 / U-125PE1E5 INDOOR MODEL S-60PT1E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 60 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-71PT1E5 / U-71PE1E5 INDOOR MODEL S-71PT1E5 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500...
  • Page 61 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-71PT1E5×2 / U-140PE1E5 INDOOR MODEL S-71PT1E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 62 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-100PT1E5 / U-100PE1E5 INDOOR MODEL S-100PT1E5 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 63 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-125PT1E5 / U-125PE1E5 INDOOR MODEL S-125PT1E5 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 64 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-140PT1E5 / U-140PE1E5 INDOOR MODEL S-140PT1E5 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 65 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×2 / U-71PE1E8 INDOOR MODEL S-36PT1E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 66 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×3 / U-100PE1E8 INDOOR MODEL S-36PT1E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 67 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-36PT1E5×4 / U-125PE1E8 INDOOR MODEL S-36PT1E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 68 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-45PT1E5×3 / U-125PE1E8 INDOOR MODEL S-45PT1E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 69 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-50PT1E5×2 / U-100PE1E8 INDOOR MODEL S-50PT1E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 70 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-50PT1E5×3 / U-140PE1E8 INDOOR MODEL S-50PT1E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 71 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-60PT1E5×2 / U-125PE1E8 INDOOR MODEL S-60PT1E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 72 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-71PT1E5 / U-71PE1E8 INDOOR MODEL S-71PT1E5 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 10900...
  • Page 73 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 3. Ceiling Type S-71PT1E5×2 / U-140PE1E8 INDOOR MODEL S-71PT1E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 74 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-100PT1E5 / U-100PE1E8 INDOOR MODEL S-100PT1E5 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 75 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-125PT1E5 / U-125PE1E8 INDOOR MODEL S-125PT1E5 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 76 Single -Type 1-1. Unit Specifi cations 3. Ceiling Type S-140PT1E5 / U-140PE1E8 INDOOR MODEL S-140PT1E5 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 77 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×2 / U-71PE1E5 INDOOR MODEL S-36PT2E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 78 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×3 / U-100PE1E5 INDOOR MODEL S-36PT2E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 15.5...
  • Page 79 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×4 / U-125PE1E5 INDOOR MODEL S-36PT2E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 80 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-45PT2E5×3 / U-125PE1E5 INDOOR MODEL S-45PT2E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 81 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-50PT2E5 / U-50PE1E5 INDOOR MODEL S-50PT2E5 PANEL MODEL OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100 5100...
  • Page 82 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-50PT2E5×2 / U-100PE1E5 INDOOR MODEL S-50PT2E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 83 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-50PT2E5×3 / U-140PE1E5 INDOOR MODEL S-50PT2E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 84 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-60PT2E5 / U-60PE1E5 INDOOR MODEL S-60PT2E5 PANEL MODEL OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 8500...
  • Page 85 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-60PT2E5×2 / U-125PE1E5 INDOOR MODEL S-60PT2E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 86 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-71PT2E5 / U-71PE1E5 INDOOR MODEL S-71PT2E5 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500...
  • Page 87 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-71PT2E5×2 / U-140PE1E5 INDOOR MODEL S-71PT2E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0...
  • Page 88 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-100PT2E5 / U-100PE1E5 INDOOR MODEL S-100PT2E5 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 89 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-125PT2E5 / U-125PE1E5 INDOOR MODEL S-125PT2E5 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 90 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-140PT2E5 / U-140PE1E5 INDOOR MODEL S-140PT2E5 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0 CAPACITY BTU/h...
  • Page 91 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×2 / U-71PE1E8 INDOOR MODEL S-36PT2E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 92 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×3 / U-100PE1E8 INDOOR MODEL S-36PT2E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 93 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-36PT2E5×4 / U-125PE1E8 INDOOR MODEL S-36PT2E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 94 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-45PT2E5×3 / U-125PE1E8 INDOOR MODEL S-45PT2E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 95 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-50PT2E5×2 / U-100PE1E8 INDOOR MODEL S-50PT2E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 96 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-50PT2E5×3 / U-140PE1E8 INDOOR MODEL S-50PT2E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2BM PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0...
  • Page 97 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-60PT2E5×2 / U-125PE1E8 INDOOR MODEL S-60PT2E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 98 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-71PT2E5 / U-71PE1E8 INDOOR MODEL S-71PT2E5 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500...
  • Page 99 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 4. Ceiling Type S-71PT2E5×2 / U-140PE1E8 INDOOR MODEL S-71PT2E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0...
  • Page 100 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-100PT2E5 / U-100PE1E8 INDOOR MODEL S-100PT2E5 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 101 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-125PT2E5 / U-125PE1E8 INDOOR MODEL S-125PT2E5 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 102 Single -Type 1-1. Unit Specifi cations 4. Ceiling Type S-140PT2E5 / U-140PE1E8 INDOOR MODEL S-140PT2E5 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0 CAPACITY BTU/h...
  • Page 103 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×2 / U-71PE1E5 INDOOR MODEL S-36PK1E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 104 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×3 / U-100PE1E5 INDOOR MODEL S-36PK1E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 105 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×4 / U-125PE1E5 INDOOR MODEL S-36PK1E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 106 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-45PK1E5×3 / U-125PE1E5 INDOOR MODEL S-45PK1E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 107 Single -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-50PK1E5 / U-50PE1E5 INDOOR MODEL S-50PK1E5 PANEL MODEL OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100...
  • Page 108 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-50PK1E5×2 / U-100PE1E5 INDOOR MODEL S-50PK1E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 109 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-50PK1E5×3 / U-140PE1E5 INDOOR MODEL S-50PK1E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 110 Single -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-60PK1E5 / U-60PE1E5 INDOOR MODEL S-60PK1E5 PANEL MODEL OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500...
  • Page 111 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-60PK1E5×2 / U-125PE1E5 INDOOR MODEL S-60PK1E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 112 Single -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-71PK1E5 / U-71PE1E5 INDOOR MODEL S-71PK1E5 PANEL MODEL OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 113 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-71PK1E5×2 / U-140PE1E5 INDOOR MODEL S-71PK1E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 114 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×2 / U-71PE1E8 INDOOR MODEL S-36PK1E5×2 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 115 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×3 / U-100PE1E8 INDOOR MODEL S-36PK1E5×3 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 116 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-36PK1E5×4 / U-125PE1E8 INDOOR MODEL S-36PK1E5×4 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 117 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-45PK1E5×3 / U-125PE1E8 INDOOR MODEL S-45PK1E5×3 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 118 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-50PK1E5×2 / U-100PE1E8 INDOOR MODEL S-50PK1E5×2 PANEL MODEL OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 119 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-50PK1E5×3 / U-140PE1E8 INDOOR MODEL S-50PK1E5×3 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 120 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-60PK1E5×2 / U-125PE1E8 INDOOR MODEL S-60PK1E5×2 PANEL MODEL OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 121 Single -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-71PK1E5 / U-71PE1E8 INDOOR MODEL S-71PK1E5 PANEL MODEL OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 122 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 5. Wall Mounted Type S-71PK1E5×2 / U-140PE1E8 INDOOR MODEL S-71PK1E5×2 PANEL MODEL OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 123 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×2 / U-71PE1E5 INDOOR MODEL S-36PF1E5×2 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 7.10 7.10 7.10 CAPACITY...
  • Page 124 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×3 / U-100PE1E5 INDOOR MODEL S-36PF1E5×3 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 125 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×4 / U-125PE1E5 INDOOR MODEL S-36PF1E5×4 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 126 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-45PF1E5×3 / U-125PE1E5 INDOOR MODEL S-45PF1E5×3 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 127 Single-Type 1-1. Unit Specifications 6. Low Silhouette Ducted Type S-50PF1E5 / U-50PE1E5 INDOOR MODEL S-50PF1E5 PANEL MODEL OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100 5100...
  • Page 128 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-50PF1E5×2 / U-100PE1E5 INDOOR MODEL S-50PF1E5×2 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 129 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-50PF1E5×3 / U-140PE1E5 INDOOR MODEL S-50PF1E5×3 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 130 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-60PF1E5 / U-60PE1E5 INDOOR MODEL S-60PF1E5 OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 6.00 6.00 6.00 CAPACITY BTU/h 20500 20500 20500...
  • Page 131 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-60PF1E5×2 / U-125PE1E5 INDOOR MODEL S-60PF1E5×2 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 132 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-71PF1E5 / U-71PE1E5 INDOOR MODEL S-71PF1E5 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 7.10 7.10 7.10 CAPACITY BTU/h 24200 24200 24200...
  • Page 133 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-71PF1E5×2 / U-140PE1E5 INDOOR MODEL S-71PF1E5×2 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 134 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-100PF1E5 / U-100PE1E5 INDOOR MODEL S-100PF1E5 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h 34100 34100...
  • Page 135 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-125PF1E5 / U-125PE1E5 INDOOR MODEL S-125PF1E5 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h 42700 42700...
  • Page 136 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-140PF1E5 / U-140PE1E5 INDOOR MODEL S-140PF1E5 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h 47800 47800...
  • Page 137 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×2 / U-71PE1E8 INDOOR MODEL S-36PF1E5×2 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 7.10 7.10 7.10 CAPACITY...
  • Page 138 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×3 / U-100PE1E8 INDOOR MODEL S-36PF1E5×3 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 139 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-36PF1E5×4 / U-125PE1E8 INDOOR MODEL S-36PF1E5×4 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 140 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-45PF1E5×3 / U-125PE1E8 INDOOR MODEL S-45PF1E5×3 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 141 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-50PF1E5×2 / U-100PE1E8 INDOOR MODEL S-50PF1E5×2 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5...
  • Page 142 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-50PF1E5×3 / U-140PE1E8 INDOOR MODEL S-50PF1E5×3 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 143 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-60PF1E5×2 / U-125PE1E8 INDOOR MODEL S-60PF1E5×2 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0...
  • Page 144 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-71PF1E5 / U-71PE1E8 INDOOR MODEL S-71PF1E5 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 7.10 7.10 7.10 CAPACITY BTU/h 24200...
  • Page 145 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-71PF1E5×2 / U-140PE1E8 INDOOR MODEL S-71PF1E5×2 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5...
  • Page 146 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-100PF1E5 / U-100PE1E8 INDOOR MODEL S-100PF1E5 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 147 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-125PF1E5 / U-125PE1E8 INDOOR MODEL S-125PF1E5 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 148 Single -Type 1-1. Unit Specifi cations 6. Low Silhouette Ducted Type S-140PF1E5 / U-140PE1E8 INDOOR MODEL S-140PF1E5 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 149 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×2 / U-71PE1E5 INDOOR MODEL S-36PN1E5×2 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500...
  • Page 150 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×3 / U-100PE1E5 INDOOR MODEL S-36PN1E5×3 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 151 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×4 / U-125PE1E5 INDOOR MODEL S-36PN1E5×4 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 152 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-45PN1E5×3 / U-125PE1E5 INDOOR MODEL S-45PN1E5×3 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 153 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-50PN1E5 / U-50PE1E5 INDOOR MODEL S-50PN1E5 PANEL MODEL OUTDOOR MODEL U-50PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 17100 17100 17100 5100...
  • Page 154 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-50PN1E5×2 / U-100PE1E5 INDOOR MODEL S-50PN1E5×2 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 155 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-50PN1E5×3 / U-140PE1E5 INDOOR MODEL S-50PN1E5×3 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 156 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-60PN1E5 / U-60PE1E5 INDOOR MODEL S-60PN1E5 OUTDOOR MODEL U-60PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 8500 24200 CURRENT...
  • Page 157 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-60PN1E5×2 / U-125PE1E5 INDOOR MODEL S-60PN1E5×2 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 158 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-71PN1E5 / U-71PE1E5 INDOOR MODEL S-71PN1E5 OUTDOOR MODEL U-71PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500 27300 CURRENT...
  • Page 159 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-71PN1E5×2 / U-140PE1E5 INDOOR MODEL S-71PN1E5×2 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 160 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-100PN1E5 / U-100PE1E5 INDOOR MODEL S-100PN1E5 OUTDOOR MODEL U-100PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h 34100 34100 34100 11300...
  • Page 161 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-125PN1E5 / U-125PE1E5 INDOOR MODEL S-125PN1E5 OUTDOOR MODEL U-125PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h 42700 42700 42700 11300...
  • Page 162 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-140PN1E5 / U-140PE1E5 INDOOR MODEL S-140PN1E5 OUTDOOR MODEL U-140PE1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h 47800 47800 47800 11300...
  • Page 163 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×2 / U-71PE1E8 INDOOR MODEL S-36PN1E5×2 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500...
  • Page 164 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×3 / U-100PE1E8 INDOOR MODEL S-36PN1E5×3 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 165 Simultaneous (Double-Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-36PN1E5×4 / U-125PE1E8 INDOOR MODEL S-36PN1E5×4 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1×3 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 166 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-45PN1E5×3 / U-125PE1E8 INDOOR MODEL S-45PN1E5×3 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 167 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-50PN1E5×2 / U-100PE1E8 INDOOR MODEL S-50PN1E5×2 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h...
  • Page 168 Simultaneous (Triple) -Type 1-1. Unit Specifi cations 7. Ducted Type S-50PN1E5×3 / U-140PE1E8 INDOOR MODEL S-50PN1E5×3 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P3HPC2 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 169 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-60PN1E5×2 / U-125PE1E8 INDOOR MODEL S-60PN1E5×2 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h...
  • Page 170 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-71PN1E5 / U-71PE1E8 INDOOR MODEL S-71PN1E5 OUTDOOR MODEL U-71PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200 8500 27300 CURRENT...
  • Page 171 Simultaneous (Twin) -Type 1-1. Unit Specifi cations 7. Ducted Type S-71PN1E5×2 / U-140PE1E8 INDOOR MODEL S-71PN1E5×2 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h...
  • Page 172 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-100PN1E5 / U-100PE1E8 INDOOR MODEL S-100PN1E5 OUTDOOR MODEL U-100PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 12.5 CAPACITY BTU/h 34100 34100...
  • Page 173 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-125PN1E5 / U-125PE1E8 INDOOR MODEL S-125PN1E5 OUTDOOR MODEL U-125PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 14.0 CAPACITY BTU/h 42700 42700...
  • Page 174 Single -Type 1-1. Unit Specifi cations 7. Ducted Type S-140PN1E5 / U-140PE1E8 INDOOR MODEL S-140PN1E5 OUTDOOR MODEL U-140PE1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.5 CAPACITY BTU/h 47800 47800...
  • Page 175 Simultaneous (Twin) -Type 1-1. Unit Specifications PEY1 1. 4-Way Cassette Type S-36PU1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 176 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-50PU1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø...
  • Page 177 Single-Type 1-1. Unit Specifications PEY1 1. 4-Way Cassette Type S-60PU1E5 / U-60PEY1E5 INDOOR MODEL S-60PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500...
  • Page 178 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-60PU1E5×2 / U-125PEY1E5 INDOOR MODEL S-60PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø...
  • Page 179 Single-Type 1-1. Unit Specifications PEY1 1. 4-Way Cassette Type S-71PU1E5 / U-71PEY1E5 INDOOR MODEL S-71PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 180 Single -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-100PU1E5 / U-100PEY1E5 INDOOR MODEL S-100PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 181 Single -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-125PU1E5 / U-125PEY1E5 INDOOR MODEL S-125PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 182 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-50PU1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø...
  • Page 183 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-60PU1E5×2 / U-125PEY1E8 INDOOR MODEL S-60PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 184 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-71PU1E5×2 / U-140PEY1E8 INDOOR MODEL S-71PU1E5×2 PANEL MODEL CZ-KPU2×2 OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø...
  • Page 185 Single -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-100PU1E5 / U-100PEY1E8 INDOOR MODEL S-100PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 186 Single -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-125PU1E5 / U-125PEY1E8 INDOOR MODEL S-125PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 187 Single -Type 1-1. Unit Specifi cations PEY1 1. 4-Way Cassette Type S-140PU1E5 / U-140PEY1E8 INDOOR MODEL S-140PU1E5 PANEL MODEL CZ-KPU2 OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 188 Simultaneous (Twin) -Type 1-1. Unit Specifications PEY1 2. 4-Way Cassette 60×60 Type S-36PY1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 189 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 2. 4-Way Cassette 60×60 Type S-50PY1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø...
  • Page 190 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 2. 4-Way Cassette 60×60 Type S-50PY1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PY1E5×2 PANEL MODEL CZ-KPY2×2 OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø...
  • Page 191 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-36PT1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PT1E5×2 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 192 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-50PT1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PT1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 193 Single-Type 1-1. Unit Specifications PEY1 3. Ceiling Type S-60PT1E5 / U-60PEY1E5 INDOOR MODEL S-60PT1E5 PANEL MODEL OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 6800 23900...
  • Page 194 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-60PT1E5×2 / U-125PEY1E5 INDOOR MODEL S-60PT1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 195 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-71PT1E5 / U-71PEY1E5 INDOOR MODEL S-71PT1E5 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 196 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-100PT1E5 / U-100PEY1E5 INDOOR MODEL S-100PT1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 197 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-125PT1E5 / U-125PEY1E5 INDOOR MODEL S-125PT1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 198 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-50PT1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PT1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 199 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-60PT1E5×2 / U-125PEY1E8 INDOOR MODEL S-60PT1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 200 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-71PT1E5×2 / U-140PEY1E8 INDOOR MODEL S-71PT1E5×2 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 201 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-100PT1E5 / U-100PEY1E8 INDOOR MODEL S-100PT1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 202 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-125PT1E5 / U-125PEY1E8 INDOOR MODEL S-125PT1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 13.5 CAPACITY...
  • Page 203 Single -Type 1-1. Unit Specifi cations PEY1 3. Ceiling Type S-140PT1E5 / U-140PEY1E8 INDOOR MODEL S-140PT1E5 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 204 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-36PT2E5×2 / U-71PEY1E5 INDOOR MODEL S-36PT2E5×2 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 205 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-50PT2E5×2 / U-100PEY1E5 INDOOR MODEL S-50PT2E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 206 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-60PT2E5 / U-60PEY1E5 INDOOR MODEL S-60PT2E5 PANEL MODEL OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500...
  • Page 207 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-60PT2E5×2 / U-125PEY1E5 INDOOR MODEL S-60PT2E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 208 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-71PT2E5 / U-71PEY1E5 INDOOR MODEL S-71PT2E5 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 209 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-100PT2E5 / U-100PEY1E5 INDOOR MODEL S-100PT2E5 PANEL MODEL OUTDOOR MODEL U100PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0 11.5 CAPACITY...
  • Page 210 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-125PT2E5 / U-125PEY1E5 INDOOR MODEL S-125PT2E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5 13.5 CAPACITY...
  • Page 211 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-50PT2E5×2 / U-100PEY1E8 INDOOR MODEL S-50PT2E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 212 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-60PT2E5×2 / U-125PEY1E8 INDOOR MODEL S-60PT2E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 213 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-71PT2E5×2 / U-140PEY1E8 INDOOR MODEL S-71PT2E5×2 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 214 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-100PT2E5 / U-100PEY1E8 INDOOR MODEL S-100PT2E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0 11.5 13.5...
  • Page 215 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-125PT2E5 / U-125PEY1E8 INDOOR MODEL S-125PT2E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 13.5 CAPACITY...
  • Page 216 Single -Type 1-1. Unit Specifi cations PEY1 4. Ceiling Type S-140PT2E5 / U-140PEY1E8 INDOOR MODEL S-140PT2E5 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0 15.0 CAPACITY...
  • Page 217 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-36PK1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PK1E5×2 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 218 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-50PK1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PK1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 219 Single-Type 1-1. Unit Specifications PEY1 5. Wall Mounted Type S-60PK1E5 / U-60PEY1E5 INDOOR MODEL S-60PK1E5 PANEL MODEL OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 6800...
  • Page 220 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-60PK1E5×2 / U-125PEY1E5 INDOOR MODEL S-60PK1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 221 Single -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-71PK1E5 / U-71PEY1E5 INDOOR MODEL S-71PK1E5 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 222 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-50PK1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PK1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 223 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-60PK1E5×2 / U-125PEY1E8 INDOOR MODEL S-60PK1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 224 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 5. Wall Mounted Type S-71PK1E5×2 / U-140PEY1E8 INDOOR MODEL S-71PK1E5×2 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 225 Simultaneous (Twin) -Type 1-1. Unit Specifications PEY1 6. Low Silhouette Ducted Type S-36PF1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PF1E5×2 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200...
  • Page 226 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-50PF1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PF1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø...
  • Page 227 Single-Type 1-1. Unit Specifications PEY1 6. Low Silhouette Ducted Type S-60PF1E5 / U-60PEY1E5 INDOOR MODEL S-60PF1E5 PANEL MODEL OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500...
  • Page 228 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-60PF1E5×2 / U-125PEY1E5 INDOOR MODEL S-60PF1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø...
  • Page 229 Single-Type 1-1. Unit Specifications PEY1 6. Low Silhouette Ducted Type S-71PF1E5 / U-71PEY1E5 INDOOR MODEL S-71PF1E5 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 230 Single -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-100PF1E5 / U-100PEY1E5 INDOOR MODEL S-100PF1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 231 Single -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-125PF1E5 / U-125PEY1E5 INDOOR MODEL S-125PF1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 232 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-50PF1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PF1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø...
  • Page 233 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-60PF1E5×2 / U-125PEY1E8 INDOOR MODEL S-60PF1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 234 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-71PF1E5×2 / U-140PEY1E8 INDOOR MODEL S-71PF1E5×2 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø...
  • Page 235 Single -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-100PF1E5 / U-100PEY1E8 INDOOR MODEL S-100PF1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 236 Single -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-125PF1E5 / U-125PEY1E8 INDOOR MODEL S-125PF1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 237 Single -Type 1-1. Unit Specifi cations PEY1 6. Low Silhouette Ducted Type S-140PF1E5 / U-140PEY1E8 INDOOR MODEL S-140PF1E5 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 238 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-36PN1E5×2 / U-71PEY1E5 INDOOR MODEL S-36PN1E5×2 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200...
  • Page 239 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-50PN1E5×2 / U-100PEY1E5 INDOOR MODEL S-50PN1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 240 Single-Type 1-1. Unit Specifications PEY1 7. Ducted Type S-60PN1E5 / U-60PEY1E5 INDOOR MODEL S-60PN1E5 PANEL MODEL OUTDOOR MODEL U-60PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 20500 20500 20500 6800 23900...
  • Page 241 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-60PN1E5×2 / U-125PEY1E5 INDOOR MODEL S-60PN1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5...
  • Page 242 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-71PN1E5 / U-71PEY1E5 INDOOR MODEL S-71PN1E5 PANEL MODEL OUTDOOR MODEL U-71PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY CAPACITY BTU/h 24200 24200 24200...
  • Page 243 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-100PN1E5 / U-100PEY1E5 INDOOR MODEL S-100PN1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 244 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-125PN1E5 / U-125PEY1E5 INDOOR MODEL S-125PN1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E5 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 1ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 245 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-50PN1E5×2 / U-100PEY1E8 INDOOR MODEL S-50PN1E5×2 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0...
  • Page 246 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-60PN1E5×2 / U-125PEY1E8 INDOOR MODEL S-60PN1E5×2 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5...
  • Page 247 Simultaneous (Twin) -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-71PN1E5×2 / U-140PEY1E8 INDOOR MODEL S-71PN1E5×2 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL CZ-P155BK1 PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0...
  • Page 248 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-100PN1E5 / U-100PEY1E8 INDOOR MODEL S-100PN1E5 PANEL MODEL OUTDOOR MODEL U-100PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 10.0 10.0 10.0...
  • Page 249 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-125PN1E5 / U-125PEY1E8 INDOOR MODEL S-125PN1E5 PANEL MODEL OUTDOOR MODEL U-125PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 12.5 12.5 12.5 13.5 CAPACITY...
  • Page 250 Single -Type 1-1. Unit Specifi cations PEY1 7. Ducted Type S-140PN1E5 / U-140PEY1E8 INDOOR MODEL S-140PN1E5 PANEL MODEL OUTDOOR MODEL U-140PEY1E8 Branch pipe MODEL PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12012 ø, Hz 1ø 50Hz 3ø 50Hz POWER SUPPLY 14.0 14.0 14.0...
  • Page 251 1-2. Dimensional Data (A) Indoor Units: S-36PU1E5 / S-45PU1E5 / S-50PU1E5 / S-60PU1E5 / S-71PU1E5 860~910 unit: mm (Ceiling opening dimensions) (Suspension bolt pitch) Less than 35 Less than 35 Less than 300 View X Raise dimension of drain tube...
  • Page 252 1-2. Dimensional Data (A) Indoor Units: S-100PU1E5 / S-125PU1E5 / S-140PU1E5 860~910 unit: mm (Ceiling opening dimensions) (Suspension bolt pitch) Less than 35 Less than 35 Less than 300 View X The length of the suspension bolts should be selected so that there is a gap of 30 mm or more below the lower surface of the ceiling (18 mm or more below the lower surface of...
  • Page 253 1-2. Dimensional Data (A) Indoor Units: S-36PY1E5, S-45PY1E5, S-50PY1E5 1-243...
  • Page 254 1-2. Dimensional Data (A) Indoor Units: S-36PT1E5, S-45PT1E5, S-50PT1E5, S-60PT1E5 S-71PT1E5, S-100PT1E5, S-125PT1E5, S-140PT1E5 Length Type 36, 45, 50 Air intake 60, 71 1125 1180 100, 125, 140 1540 1595 Ceiling side 27.5 27.5 Air outlet Unit: mm (Suspension bolt pitch) (Liquid tubing •...
  • Page 255 1-2. Dimensional Data (A) Indoor Units: S-36PT2E5, S-45PT2E5, S-50PT2E5 unit :mm Detailed view of intaking Distance of each exposed bolt must be of equal length outside air duct connection port within 50mm. Suspension bolt Unit Ceiling surface Bracket (Suspension bolt pitch) Over Over discharge...
  • Page 256 1-2. Dimensional Data (A) Indoor Units: S-60PT2E5, S-71PT2E5 unit :mm Detailed view of intaking Distance of each exposed bolt must be of equal length outside air duct connection port within 50mm. Suspension bolt Unit Ceiling surface 1226 (Suspension bolt pitch) Bracket 1269 Over...
  • Page 257 1-2. Dimensional Data (A) Indoor Units: S-100PT2E5, S-125PT2E5, S-140PT2E5 unit :mm Detailed view of intaking Distance of each exposed bolt must be of equal length outside air duct connection port within 50mm. Suspension bolt Unit Ceiling surface 1541 Bracket (Suspension bolt pitch) 1584 Over Over...
  • Page 258: Front View

    1-2. Dimensional Data (A) Indoor Units: S-36PK1E5, S-45PK1E5, S-50PK1E5, S-60PK1E5 S-71PK1E5 unit: mm Refrigerant tubing (liquid tube) S36 - S50: ø6.35 (flared) S60 - S71: ø9.52 (flared) Refrigerant tubing (gas tube) S36 - S50: ø12.7 (flared) S60 - S71: ø15.88 (flared) FILTER SIZE Drain hose VP13 (outer dia.
  • Page 259 1-2. Dimensional Data (A) Indoor Units: S-36PF1E5, S-45PF1E5, S-50PF1E5, S-60PF1E5 S-71PF1E5, S-100PF1E5, S-125PF1E5, S-140PF1E5 Unit: mm Type 36, 45, 50 450 (Pitch 150 × 3) 60, 71 1,067 1,000 750 (Pitch 150 × 5) 100, 125, 140 1,467 1,400 1,050 (Pitch 150 × 7) 1,192 a) Refrigerant tubing joint (liquid tube) b) Refrigerant tubing joint (gas tube)
  • Page 260 1-2. Dimensional Data (A) Indoor Units: S-36PN1E5, S-45PN1E5, S-50PN1E5 POSITION OF SUSPENSION BOLT (unit:mm) TYPE S-36PN1E5 S-45PN1E5 S-50PN1E5 S-60PN1E5 1060 1000 S-71PN1E5 S-100PN1E5 1260 1200 S-125PN1E5 S-140PN1E5 NOTE NAME Q'TY Pipe connection (gas) O.D. Ø12.7 Flared Pipe connection (liquid) O.D. Ø6.35 Flared Drain pipe connection Female screw PT1"...
  • Page 261 1-2. Dimensional Data (A) Indoor Units: S-60PN1E5, S-71PN1E5 Q'TY NOTE NAME Pipe connection (gas) O.D. Ø15.88 Flared Pipe connection (liquid) O.D. Ø9.52 Flared Drain pipe connection Female screw PT1" Duct connection Hanger 845 (P65 x 13) 57.5 Control box Air Flow 28-Ø4.5 30-Ø4.5 780 (P65 x 12)
  • Page 262 1-2. Dimensional Data (B) Outdoor Unit: U-50PE1E5 U-60PEY1E5 / U-71PEY1E5 (97) Drain port Air intake Air intake Drain port Air discharge (161) Refrigerant tubing joint (liquid tube) Unit: mm (157) Flare connection ø6.35 mm (50) ø9.52 mm (60, 71) Refrigerant tubing joint (gas tube) Flare connection ø12.7 mm (50) ø15.88 mm (60, 71) 1-252...
  • Page 263 1-2. Dimensional Data (B) Outdoor Units: U-60PE1E5 / U-71PE1E5/ U-100PEY1E5/ U-125PEY1E5 U-71PE1E8 / U-100PEY1E8/ U-125PEY1E8 unit: mm Mounting hole (4-R6.5), anchor bolt: M10 Refrigerant piping (liquid pipe), flared connection (ø9.52) Refrigerant piping (gas pipe), flared connection (ø15.88) Electrical wiring port ( ø13) ø22) Electrical wiring port (...
  • Page 264 1-2. Dimensional Data (B) Outdoor Units: U-100PE1E5 / U-125PE1E5 / U-140PE1E5 U-100PE1E8 / U-125PE1E8 / U-140PE1E8 / U-140PEY1E8 unit: mm Mounting hole (4-R6.5), anchor bolt: M10 Refrigerant piping (liquid pipe), flared connection (ø9.52) Refrigerant piping (gas pipe), flared connection (ø15.88) Electrical wiring port (ø13) Electrical wiring port (ø22) Electrical wiring port (ø27)
  • Page 265 1-3. Refrigerant Flow Diagram Outdoor Unit: U-50PE1E5 Indoor Unit: Accumulator Compressor Gas line service valve ø12.7 Flare connection High pressure switch Muffler Muffler Heat exchanger 4-way valve Heat exchanger Distributor Strainer Electronic ref. Liquid line control valve service valve ø6.35 Flare connection Strainer Cooling cycle...
  • Page 266 1-3. Refrigerant Flow Diagram Outdoor Units: U-60PE1E5 / U-71PE1E5 Indoor Unit U-71PE1E8 High pressure 4-way switch valve Muffler ø15.88 Outdoor-air Heat Temp Thermistor exchanger Suction Temp Heat exchanger Thermistor Temp Thermistor Heat exchanger Discharge Temp Distributor Thermistor Defrost Temp Thermistor Strainer Distributor ø9.52...
  • Page 267 1-3. Refrigerant Flow Diagram Outdoor Units: U-100PEY1E5 / U-100PEY1E8 : t i Indoor Unit: High pressure 4-way switch valve ø15.88 Outdoor-air Heat Temp Thermistor exchanger Suction Temp Heat exchanger Thermistor Temp Thermistor Discharge Temp Thermistor Heat exchanger Distributor Defrost Temp Thermistor Strainer Distributor...
  • Page 268 1-4. Operationg Range Type PE1 Temperature Indoor air intake temp. Outdoor air intake temp. Maximum 32°C DB / 25°C WB 46°C DB Cooling Minimum 18°C DB / 14°C WB -15°C DB Maximum 30°C DB / − WB 24°C DB/18°C WB Heating Minimum 16°C DB / −...
  • Page 269 1-5. Capacity Correction Graph According to Temperature Condition U-50PE1E5 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp. ( °C DB) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 24 °CDB 20 °CDB...
  • Page 270 1-5. Capacity Correction Graph According to Temperature Condition U-60PE1E5 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 16 °CDB 20 °CDB 22°CWB 19°CWB 24 °CDB...
  • Page 271 1-5. Capacity Correction Graph According to Temperature Condition U-71PE1E5 (For 50 Hz) / U-71PE1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 16 °CDB 20 °CDB 22°CWB...
  • Page 272 1-5. Capacity Correction Graph According to Temperature Condition U-100PE1E5 (For 50 Hz) / U-100PE1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB...
  • Page 273 1-5. Capacity Correction Graph According to Temperature Condition U-125PE1E5 (For 50 Hz) / U-125PE1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB...
  • Page 274 1-5. Capacity Correction Graph According to Temperature Condition U-140PE1E5 (For 50 Hz) / U-140PE1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB...
  • Page 275 1-5. Capacity Correction Graph According to Temperature Condition PEY1 U-60PEY1E5 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp. ( °C DB) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) 24 °CDB 20 °CDB 16 °CDB...
  • Page 276 1-5. Capacity Correction Graph According to Temperature Condition PEY1 U-71PEY1E5 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp. ( °C DB) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 24 °CDB 20 °CDB...
  • Page 277 1-5. Capacity Correction Graph According to Temperature Condition PEY1 U-100PEY1E5 (For 50 Hz) / U-100PEY1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB...
  • Page 278 1-5. Capacity Correction Graph According to Temperature Condition PEY1 U-125PEY1E5 (For 50 Hz) / U-125PEY1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB...
  • Page 279: Capacity Correction Graph According To Temperature Condition

    1-5. Capacity Correction Graph According to Temperature Condition PEY1 U-140PEY1E8 (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) 16 °CDB 20 °CDB 24 °CDB 22°CWB 19°CWB 16°CWB Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 22°CWB 19°CWB 16°CWB...
  • Page 280: Noise Criterion Curves

    1-6. Noise Criterion Curves (A) Indoor Units: 4 WAY Cassette Type High : S-36PU1E5 : S-45PU1E5 MODEL MODEL SOUND LEVEL : High 30 dB(A) SOUND LEVEL : High 31 dB(A) 27 dB(A) 27 dB(A) CONDITION : Under the unit 1.5m CONDITION : Under the unit 1.5m...
  • Page 281: Way Cassette 60×60 Type (Y1)

    1-6. Noise Criterion Curves (A) Indoor Units: 4 WAY Cassette Type High : S-71PU1E5 : S-100PU1E5 MODEL MODEL : High 37 dB(A) : High 44 dB(A) SOUND LEVEL SOUND LEVEL 28 dB(A) 32 dB(A) : Under the unit 1.5m CONDITION CONDITION : Under the unit 1.5m : 220-230-240V, 1 phase, 50Hz...
  • Page 282 1-6. Noise Criterion Curves (A) Indoor Units: 4 WAY Cassette 60×60 Type Both 50Hz / 60Hz Strong Weak MODEL : S-45PY1E5 MODEL : S-36PY1E5 SOUND LEVEL : High 36 dB(A) SOUND LEVEL : High 32 dB(A) 28 dB(A) 26 dB(A) CONDITION : 1.5 m directly below unit CONDITION...
  • Page 283: Ceiling Type (T1)

    1-6. Noise Criterion Curves (A) Indoor Units: Both 50Hz / 60Hz High Ceiling Type : S-36PT1E5 : S-45PT1E5 MODEL MODEL S-50PT1E5 : High 35 dB(A) : High 38 dB(A) SOUND LEVEL SOUND LEVEL 30 dB(A) 30 dB(A) CONDITION CONDITION : 1 m from front of outlet at height of 1 m : 1 m from front of outlet at height of 1 m : 220-230-240V, 1 phase, 50Hz : 220-230-240V, 1 phase, 50Hz...
  • Page 284: Ceiling Type (T2)

    1-6. Noise Criterion Curves (A) Indoor Units: Both 50Hz / 60Hz High Ceiling Type : S-36PT2E5 : S-45PT2E5 MODEL MODEL S-50PT2E5 High 36 dB(A) High 37 dB(A) SOUND LEVEL : SOUND LEVEL : 29 dB(A) 29 dB(A) CONDITION CONDITION : 1 m from front of outlet at height of 1 m : 1 m from front of outlet at height of 1 m : 220-230-240V, 1 phase, 50Hz : 220-230-240V, 1 phase, 50Hz...
  • Page 285 1-6. Noise Criterion Curves (A) Indoor Units: Both 50Hz / 60Hz High Ceiling Type : S-100PT2E5 : S-125PT2E5 MODEL MODEL High 42 dB(A) High 46 dB(A) SOUND LEVEL : SOUND LEVEL : 35 dB(A) 36 dB(A) CONDITION CONDITION : 1 m from front of outlet at height of 1 m : 1 m from front of outlet at height of 1 m : 220-230-240V, 1 phase, 50Hz : 220-230-240V, 1 phase, 50Hz...
  • Page 286: Wall Mounted Type (K1)

    1-6. Noise Criterion Curves (A) Indoor Units: Both 50Hz / 60Hz Wall Mounted Type Strong Weak MODEL : S-36PK1E5 MODEL : S-45PK1E5 SOUND LEVEL : STRONG 35 dB(A) SOUND LEVEL : STRONG 38 dB(A) High 31 dB(A) High 34 dB(A) 27 dB(A) 30 dB(A) CONDITION...
  • Page 287: Low Silhouette Ducted Type (F1)

    1-6. Noise Criterion Curves (A) Indoor Units High Low Silhouette Ducted Type : S-36PF1E5 : S-45PF1E5 MODEL MODEL 33 dB(A) SOUND LEVEL : High 33 dB(A) SOUND LEVEL : High 25 dB(A) 25 dB(A) CONDITION : Under the unit 1.5m CONDITION : Under the unit 1.5m : 220-230-240V, 1 phase, 50Hz...
  • Page 288 1-6. Noise Criterion Curves (A) Indoor Units High Low Silhouette Ducted Type : S-100PF1E5 : S-125PF1E5 MODEL MODEL 39 dB(A) SOUND LEVEL : High 38 dB(A) SOUND LEVEL : High 31 dB(A) 32 dB(A) CONDITION : Under the unit 1.5m CONDITION : Under the unit 1.5m : 220-230-240V, 1 phase, 50Hz...
  • Page 289 1-6. Noise Criterion Curves (A) Indoor Units High Ducted Type MODEL : S-36PN1E5 MODEL : S-45PN1E5 S-50PN1E5 SOUND LEVEL SOUND LEVEL : HIGH 40 dB(A) : HIGH 41 dB(A) 35 dB(A) 35 dB(A) CONDITION CONDITION : Under the unit 1.5m : Under the unit 1.5m SOURCE SOURCE...
  • Page 290: (B) Outdoor Units

    1-6. Noise Criterion Curves (B) Outdoor Unit MODEL : U-50PE1E5 MODEL : U-50PE1E5 : Cooling 46 dB(A) : Heating 50 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
  • Page 291 1-6. Noise Criterion Curves (B) Outdoor Unit MODEL : U-60PE1E5 MODEL : U-60PE1E5 : Cooling 48 dB(A) : Heating 50 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
  • Page 292 1-6. Noise Criterion Curves (B) Outdoor Unit : U-100PE1E5, U-100PE1E8 MODEL : U-100PE1E5, U-100PE1E8 MODEL : Cooling 52 dB(A) : Heating 52 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
  • Page 293 1-6. Noise Criterion Curves (B) Outdoor Unit : U-140PE1E5, U-140PE1E8 MODEL : U-140PE1E5, U-140PE1E8 MODEL : Cooling 54 dB(A) : Heating 55 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
  • Page 294 1-6. Noise Criterion Curves (B) Outdoor Unit : U-60PEY1E5 : U-60PEY1E5 MODEL MODEL : Cooling 46 dB(A) : Heating 50 dB(A) SOUND LEVEL SOUND LEVEL CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m : 220-230-240V, 1 phase, 50Hz : 220-230-240V, 1 phase, 50Hz SOURCE...
  • Page 295 1-6. Noise Criterion Curves (B) Outdoor Unit MODEL : U-100PEY1E5, U-100PEY1E8 MODEL : U-100PEY1E5, U-100PEY1E8 : Cooling 54 dB(A) : Heating 54 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
  • Page 296 1-6. Noise Criterion Curves (B) Outdoor Unit : U-140PEY1E8 MODEL MODEL : U-140PEY1E8 SOUND LEVEL : Cooling 54 dB(A) : Heating 53 dB(A) SOUND LEVEL : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m CONDITION SOURCE : 380-400-415V, 3 phase, 50Hz...
  • Page 297: Indoor Fan Performance

    1-7. Indoor Fan Performance External Static Pressure Setting for AC Fan Motor Model To apply to following models S-36PN1E5 , S-45PN1E5 , S-50PN1E5 There are two tap connector located in indoor unit control box can be selected. The "blue connector" is standard tap ,use-as-is at shipment. For high static pressure duct ,switch Fan Motor connector to plug in boost tap "white connector"...
  • Page 298: Airflow Distance Chart

    1-8. Airflow Distance Chart 4-Way Cassette Type S-60PU1E5 / 71PU1E5 Heating : Distribution of wind velocity ) ° ° 0 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature ) ° ° 0 Horizontal air flow distance (m) Cooling : Distribution of wind velocity ) °...
  • Page 299 S-100PU1E5 / 125PU1E5 / 140PU1E5 Heating : Distribution of wind velocity ) ° ° 0 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature ) ° ° 0 Horizontal air flow distance (m) Cooling : Distribution of wind velocity ) °...
  • Page 300 Ceiling Type (T2 Type) S-36PT2E5 / 45PT2E5 / 50PT2E5 Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
  • Page 301 S-60PT2E5 / 71PT2E5 Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
  • Page 302 S-100PT2E5 / 125PT2E5 / 140PT2E5 Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
  • Page 303: Intaking Fresh Air Of 4-Way Cassette Type

    1-9. Intaking Fresh Air of 4-Way cassette Type Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
  • Page 304 • U1, Y1 Types When an External Air Intake Flange (ø100) is in Use With the External Air Intake Flange Attached External Air Intake Volume and Resistance and Operation Noise Characteristics within the Unit U1 Type Y1 Type Duct (ø100) for Connecting the External Air Intake Flange Operation Noise (External Air Intake Only)
  • Page 305: Electrical Wiring

    1-10. Electrical Wiring General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided in the exclusive line.
  • Page 306 Wiring System Diagrams * 3-phase model connections Indoor unit (No. 1) Power supply Outdoor unit (3-phase) 220/230/240V ~50Hz INV unit Power supply Ground Remote 380/400/415V, 3 N~, 50Hz controller Ground Ground Ground Indoor unit * Single-phase model connections (No. 2) Power supply Ground 220/230/240V ~50Hz...
  • Page 307 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 308 How to connect wiring to the terminal For stranded wiring (1) Cut the wire end with cutting pliers, Stranded wire Special Screw then strip the insulation to expose washer the stranded wiring about 10 mm and Ring tightly twist the wire ends. (Fig. 1-1) pressure Ring pressure terminal...
  • Page 309 Wiring samples T1 type Y1 type Functional ground screw (External Electronic Expansion Valve Kit and Schedule Timer) Protective ground screw Remote Control Wiring Power Supply Inter-unit Control Wiring Use this screw when connecting the shield Use this screw when connecting the shield for the Inter-unit control wiring to ground.
  • Page 310: Installation Instructions

    1-11. Installation instructions U-50PE1E5, U-60PEY1E5, U-71PEYE5 ACCESSORIES SUPPLIED WITH OUTDOOR UNIT Part Name Figure Q’ty Remarks Part Name Figure Q’ty Remarks Operating Installation Included this A5-size Instructions Instructions instructions SELECTING THE INSTALLATION SITE AVOID: heat sources and exhaust fans, etc. Exhaust fan damp, humid or uneven locations.
  • Page 311 (3) Obstructions on the front side and above the unit (Left side, right side and rear side are opened). 50 cm 30 cm or more or more In case of multiple installations Air intake Air intake Provide a solid base (concrete block, 10 × 40 cm beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life.
  • Page 312 Precautions for Installation in Heavy Snow Areas The platform should be higher than the maximum snow depth +50 cm. The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit. The platform foundation must be firm and the unit must be secured with anchor bolts.
  • Page 313 Tubing Size (A) Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The lengths of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible.
  • Page 314 Table 1-2 Tubing Data for Models (Single, Twin) U-60PEY1E5 Models U-50PE1E5 Tubing Data U-71PEY1E5 Liquid tube mm (in.) 6.35 (1/4) 9.52 (3/8) Tubing size outer diameter Gas tube mm (in.) 12.7 (1/2) 15.88 (5/8) Limit of tubing length 50 * Outdoor unit is placed higher Limit of elevation difference...
  • Page 315 CAUTION 1. This unit requires no additional refrigerant charge up to tubing length 20 m (50 type: 30 m). In case of more than 20 m (50 type: 30 m), additional refrigerant charge is required. 2. In case of multi type installation, indoor units should be installed within the same room. If multi type indoor units are installed in different rooms, temperature control may develop problems because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main unit).
  • Page 316 HOW TO INSTALL THE OUTDOOR UNIT Installing the Outdoor Unit Use concrete or a similar material to make the base, and ensure good drainage. Ordinarily, ensure a base height of 5 cm or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 15 cm or more at the feet on both sides of the unit.
  • Page 317 HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes that run between indoor and outdoor units.
  • Page 318 Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks.
  • Page 319 For the flare nuts at tubing connections, be sure to use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table below. Tightening torque Tube diameter Tube thickness...
  • Page 320 Insulating the Refrigerant Tubing Tubing Insulation Thermal insulation must be applied to all units tubing, Two tubes arranged together including distribution joint (purchased separately). Inter-unit Gas tube * For gas tubing, the insulation material must be heat control resistant to 120°C or above. For other tubing, it must be wiring Liquid tube heat resistant to 80°C or above.
  • Page 321 Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 322 LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) efficiency drops...
  • Page 323 Leak Test (1) With the service valves on the outdoor unit closed, remove the 6.35 mm flare nut and its bonnet on the gas tube service valve. (Save for reuse.) (2) Attach a manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
  • Page 324 Charging Additional Refrigerant Charging additional refrigerant (calculated from the liquid tube length as shown in “Amount of additional refrigerant charge”) using the liquid tube service valve. Use a balance to measure the refrigerant accurately. If the additional refrigerant charge amount cannot be charged at once, charge the remaining refrigerant in liquid form by using the gas tube service valve with the system in Cooling mode at the time of test run.
  • Page 325: Electrical Wiring

    ELECTRICAL WIRING General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided in the exclusive line.
  • Page 326: Outdoor Unit

    Wiring System Diagrams Indoor unit (No. 1) Outdoor unit (single-phase) Power supply INV unit 220/230/240 V ~ 50Hz Power supply 220/230/240 ~ 50/60 Hz Ground Remote controller Ground Ground Ground Indoor unit Ground (No. 2) Power supply 220/230/240 V ~ 50Hz Ground Outdoor Unit NOTE...
  • Page 327 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 328 How to connect wiring to the terminal Air Purging with a Vacuum Pump (for Test Run) Preparation Stranded wire (1) Cut the wire end with cutting pliers, then strip the insulation to expose the stranded wire about 10 mm and tightly twist the wire ends. Ring pressure terminal...
  • Page 329 TEST RUN Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all electrical connections are tight. (3) The protective spacers for the compressor used for transportation have been removed.
  • Page 330 U1, Y1, T1, F1, N1 Types Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2). * If multiple indoor units are used, also refer to section “System Control”.
  • Page 331 Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. (2) Fully open the closed valves on the liquid-tube and gastube sides. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
  • Page 332 Table of Self-Diagnostic Functions and Corrections (U1, Y1, T1, F1, N1 Types) Cause Wired Indoor Control by remote unit Simultaneous-operation Correction main-sub controller receiver 1:1 connection (single type) Group connection multi system remote display lamp (flexible combination) controllers Remote controller is not Remote controller is not Same at left Same at left Connect the remote...
  • Page 333 System Control System address rotary switch (Set to “0” at the time of shipment.) System control refers to the link wiring connection Inter-unit control wiring Ground for control of simultaneous-operation multi Outdoor unit For a simultaneous-operation Leakage breaker systems, group control, multi system, a maximum of 2 indoor units can be connected and mainsub remote controller control.
  • Page 334 (Wiring procedure) Connect the remote controller to the indoor unit remote control wiring terminal board (1, 2). (Remote control wiring) (2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way.
  • Page 335 Automatic address setting using the remote controller When the outdoor unit shown in “Basic wiring diagram 2” is used for group control of multiple units, use the remote controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the remote controller display.) Press the remote controller timer time button and...
  • Page 336 Connecting 2 remote controllers Connecting 2 remote controllers to control a to control 1 indoor unit simultaneous-operation multi system Remote controller Remote controller Remote controller Remote controller (main) (main) (sub) (sub) Remote control Optional Optional Optional Optional communication wiring Remote control wiring Terminal board for remote control Terminal board for...
  • Page 337 K1 Type Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2). * If multiple indoor units are used, also refer to section “System Control”...
  • Page 338 Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. (2) Fully open the closed valves on the liquid tube and gas tube sides. Preparation for Test Run Switching the temperature sensor Temperature sensors are contained in the indoor unit and wireless remote controller.
  • Page 339 Test Run Indoor control unit switch Using the control unit (1) Change the indoor control unit switch from “ON” → “TEST”. (The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is stopped.) TEST (2) All the indicator lamps blink while the test run is in progress.
  • Page 340 Table of Self-Diagnostic Functions and Corrections (K1 Type) Wired Cause remote controller Indoor unit Correction Group connection display receiver lamp 1:1 connection (Single type) (Simultaneous multi system) (Field supply) Indoor operation switch is OFF. Same at left Set the indoor operation switch ON. Nothing is Nothing is Turn ON the indoor unit power.
  • Page 341 System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and mainsub remote controller control. Basic wiring diagram 1 Single type and simultaneous-operation multi system Simultaneous-operation multi system Up to 2 (Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) Be careful to avoid miswiring when connecting...
  • Page 342 Basic wiring diagram 2 Group control (when a central control device is not used) A maximum of 8 indoor units can be connected to a single remote controller. Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system address (refrigerant system address) before turning ON the remote power switch.
  • Page 343 Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2,...) System address System address Outdoor unit control PCB System address 10s digit 1s place (2P DIP switch) (Rotary switch) System address rotary switch Both OFF (Set to “0”...
  • Page 344 Indoor unit remote controller main-sub setting When multiple wall mounted indoor units are installed for group control in a simultaneous-operation multi system, set the control PCB at the No. 2 and following wall mounted units to “Sub remote control”. If a wired remote controller is used, set the wired remote controller to “Sub”. If 2 wireless remote controllers are used, set the wireless PCB (DIP switch) on the second remote controller to “Sub”.
  • Page 345 U1, T1, F1, N1 Types (for Link Wiring) Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2 < Twin >). This test run explanation describes primarily the procedure when using the wired remote controller.
  • Page 346 Test Run Procedure See section “Items to Check Before the Recheck the items to check before the test run. Test Run” for U1, T1, F1, N1 Types (for Link Wiring). See section “Basic wiring diagram” Check the combination (wiring) of indoor and outdoor units. for U1, T1, F1, N1 Types (for Link Wiring).
  • Page 347 Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. (2) Fully open the closed valves on the liquid tube and gas tube sides. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
  • Page 348 Automatic Address Setting Basic wiring diagram Link wiring N OTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug shortcircuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes” to “No”). A maximum of 8 indoor units can be connected to 1 remote controller for group control.
  • Page 349 Case 2 If the power cannot be turned ON separately for the indoor and outdoor units in each system: The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work. Be sure to use a jig for short-circuiting.
  • Page 350 Case 4 If the power cannot be turned ON separately for the indoor and outdoor units in each system: (The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.) All-systems automatic address setting: Display item code “AA”.
  • Page 351 Checking indoor unit addresses Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode, “ALL” appears on the remote controller). Then press the button and select the indoor address.
  • Page 352 K1 Type (for Link Wiring) Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2). If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to be identified.
  • Page 353 Test Run Procedure (See section “Items to Check Before Recheck the items to check before the test run. the Test Run” for K1 Type .) (See section “Basic wiring diagram” Check the combination (wiring) of indoor and outdoor units. for K1 Type (for Link Wiring).) Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit)
  • Page 354 Table of Self-Diagnostic Functions and Corrections (K1 Type) Wired Cause remote Indoor unit Correction Group connection and simultaneous-operation controller receiver lamp display multi system Remote controller is not connected with indoor unit Connect the remote controller correctly. Nothing is Nothing is correctly.
  • Page 355 Automatic Address Setting Basic wiring diagram Link wiring N OTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes” to “No”). A maximum of 8 indoor units can be connected to 1 remote controller for group control.
  • Page 356 System address System address System address 10s digit 1s place (2P DIP switch) (Rotary switch) Both OFF “0” setting 0 Automatic address (Setting at shipment = “0”) Both OFF “1” setting 1 (If outdoor unit is No. 1) Both OFF “2”...
  • Page 357 Case 2 If the power cannot be turned ON separately for the indoor and outdoor units in each system: The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work. Be sure to use a jig for short-circuiting.
  • Page 358 Remote controller setting mode To set the remote controller main/sub setting or change the sensor, follow the steps below. (1) Press both buttons on the remote controller for more than 4 seconds together. (2) Select CODE No. with ) buttons. (3) Change DATA with (TIMER) buttons.
  • Page 359 Y1 Type (for Link Wiring) Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2 < Twin >). This test run explanation describes primarily the procedure when using the wired remote controller.
  • Page 360 Test Run Procedure (See section “Items to Check Before the Recheck the items to check before the test run. Test Run” for Y1 Type (for Link Wiring).) See section “Basic wiring diagram” Check the combination (wiring) of indoor and outdoor units. for Y1 Type (for Link Wiring).
  • Page 361 Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. (2) Fully open the closed valves on the liquid-tube and gas-tube sides. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
  • Page 362 Automatic Address Setting Basic wiring diagram Link wiring N OTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes” to “No”). A maximum of 8 indoor units can be connected to 1 remote controller for group control.
  • Page 363 Case 2 If the power cannot be turned ON separately for the indoor and outdoor units in each system: The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work. Be sure to use a jig for short-circuiting.
  • Page 364 Case 4 If the power cannot be turned ON separately for the indoor and outdoor units in each system: (The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.) All-systems automatic address setting: Display item code “AA”.
  • Page 365 Checking indoor unit addresses Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode, “ALL” appears on the remote controller). Then press the button and select the indoor address.
  • Page 366 Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. CAUTION This outdoor unit cannot collect more than the rated refrigerant amount as shown by the nameplate on the back.
  • Page 367: U-60Pe1E5 ~ U-140Pe1E5, U-71Pe1E8 ~ U-140Pe1E8

    U-60PE1E5 ~ U-140PE1E5, U-71PE1E8 ~ U-140PE1E8 U-100PEY1E5, U-125PEY1E5, U-100PEY1E8, U-125PEY1E8, U-140PEY1E8 ACCESSORIES SUPPLIED WITH OUTDOOR UNIT The following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit. Part name Q’ty Diagram Application Part name...
  • Page 368 SELECTING THE LOCATION FOR INSTALLATION SERVICE When installing multiple units, allow enough space in between the units and the side of the building. (A) If there are obstacles at the intake If the upper part is open (unit: mm) For separate installation location •...
  • Page 369 (B) If there are obstacles at the discharge If the upper part is open (unit: mm) For separate installation location For multiple units (more than 2 units) If there are obstacles above the unit (unit: mm) For separate installation location For multiple units (more than 2 units) If there are obstacles on both the intake and discharge If there is an obstacle that is higher than the unit on the intake side.
  • Page 370 If there is an obstacle that is higher than the unit on the discharge side. Pattern 2 (There is no limit to the height of theobstacle above the discharge.) If the upper part is open (unit: mm) For separate installation location For multiple units (more than 2 units) If there are obstacles above the unit (unit: mm)
  • Page 371 TRANSPORT AND INSTALL THE OUTDOOR UNIT Transporting 1. Transport the outdoor unit in its original packaging as close as possible to the installation location. 2. In the event that the unit needs to be lifted or suspended, use a rope or belt and use cloth or wood as padding to avoid damaging the unit.
  • Page 372 Precautions when operating the 3-way valve for piping installation Do not open the 3-way valve until the piping installation is completed. Valve shaft • It is closed during shipment. Service port • During installation the side panel may warp if only the flare nut is Valve cap loosened and tightened with a torque wrench.
  • Page 373 Precautions for flare nut installation Dimensions when adding flare nuts and the tightening torque (unit: mm) Piping size Tightening torque Flare section dimensions A Flare configuration 14.2N•m ~ 17.2N•m 8.7 ~ 9.1 ø 6.35 {1.4kgf•m ~ 1.7kgf•m} 32.7N•m ~ 39.9N•m 12.8 ~ 13.2 ø...
  • Page 374 Charging with refrigerant For the type PE1 At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. If the equivalent pipe length used will be 30m or less, no additional charging will be necessary. If the equivalent pipe length will be between 30 and 50 / 75m, charge with additional refrigerant according to the equivalent length given in the table below.
  • Page 375 ELECTRICAL WIRING This air conditioner must be installed in accordance with national wiring regulations. Cables connected to outdoor unit must be approved polychloroprene sheathed type 60245 IEC 57 or H05RN-F/H07RN-F or heavier. The units must be connected to the supply cables for fixed wiring by qualified technician. Circuit breaker must be incorporated in the fixed wiring in accordance with the national wiring regulations.
  • Page 376 OUTDOOR UNIT/3-PHASE MODEL OUTDOOR UNIT/SINGLE-PHASE MODEL Power supply (220/230/240V~) Power supply (380/400/415V 3N~) Power supply (220/230/240V~) Power supply (220/230/240V~) Circuit breaker Circuit breaker Circuit breaker Circuit breaker Switch Switch Switch Switch Earth Earth Earth Earth Indoor unit Outdoor unit Indoor unit Outdoor unit Wired remote controller Wired remote controller...
  • Page 377 COMBINATION OF INDOOR UNIT CONNECTION Twin, Triple and Double Twin Type Connections for PE1 Type Two, three or four indoor units can be operated simultaneously with a single remote controller. Note that individual operation is not possible. Master unit and slave unit can be set automatically in twin and triple system. No address setting is necessary.
  • Page 378 Piping Connections For PE1 Type The following table shows the pipe diameter. (Branch pipe kit should be used) (unit: mm) Indoor unit combination Outdoor unit main pipe Branch pipe diameter diameter (mm) S-36 S-45 S-50 S-60 S-71 Liquid side ø6.35 ø6.35 ø6.35 ø9.52...
  • Page 379 (TWIN type) Indoor unit Indoor unit Branch pipe Main pipe (TRIPLE type) Indoor unit Indoor unit Indoor unit Branch pipe Main pipe (DOUBLE TWIN type) Indoor unit Indoor unit Indoor unit Indoor unit Pipe branch 2 Pipe branch 2 Pipe branch 1 Main pipe •...
  • Page 380 Refrigerant charging For PE1 Type For the twin connection, the amount of refrigerant required for pipe length 30m has been included in this unit at the factory while that required for pipe length 20m has been included for the triple/double-twin connections. No additional charge is required for the first 30m pipe length in the case of the twin connection and for the first 20m in the case of the triple/double-twin connections.
  • Page 381 PRECAUTIONS REGARDING TEST RUN Check Before Test Run Content check Power supply cable Is the wire set up and connected as described in the instructions? Indoor/outdoor connection wire Check for any phase sequence. Earth wire Are the wire connection’s screws loose? Is the open and close device / leakage breaker installed? Is the power supply cable’s thickness and length appropriately measured as described in the instructions?
  • Page 382 Outdoor main PCB CHK pin RUN pin MODE pin *MODE pin: factory setting is cooling operation mode. CHECKS AFTER INSTALLATION HAVE COMPLETED Check the following items after completing installation. Is there a short circuit with the intake air flow? Is the insulation secure? (Refrigerant piping) Are there any errors with the wiring? Are the terminal screws loose? Tightening torque (Unit: N •...
  • Page 383 Optional Distribution Joint Kits CZ-P155BK1 Prior to undertaking the installation work, read carefully through the “Installation Instructions” for the air conditioner and this “Installation Instructions”. This line branch pipe is used for the R410A refrigerant. 1. Details of parts supplied Unit : mm (in.) 1 Liquid side branch pipe (inner diameter) 2 Gas side branch pipe (inner diameter)
  • Page 384 2-1 Installation Instructions Output (1) To next branch pipe or indoor unit Output (2) Refrigerant pipe Refrigerant pipe To the outdoor unit or Gas side / Liquid side next branch pipe Input branch pipe If the size of the selected refrigerant pipe and the size of the branch pipe differ, cut the connecting section with pipe cutters per the illustration at right.
  • Page 385 CZ-P3HPC2 Unit : mm CZ-P3HPC2 (for simultaneous Triple) Liquid distribution joint for liquid tube Gas distribution joint for gas tube Dowel pin position BCUP-3 (3 locations) ø12.7 ø25.4 Liquid-tube side tube connector Gas-tube side tube connector Gas-tube side tube connector ø19.05 ø28.58 ø19.05...
  • Page 386 Installing Distribution Joint Kit (for Triple) (CZ-P3HPC2) Only the distribution joints are horizontal with Check the system combination before installing the respect to the ground. The collective tubes are vertical with respect to the ground. distribution joints. Three indoor units must be installed within the The collective tube and distribution same room.
  • Page 387: Indoor Unit

    1. SELECTING THE INSTALLATION SITE 4-Way Cassette Type 4-Way Cassette Type (U1) Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near heat sources which may affect the performance of the unit.
  • Page 388 HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette Type (U1 Type) Note: For DC Fan Tap Change Procedure for 4-Way Cassette, see page 1-339. Preparation for Suspending Hole-in-anchor This unit uses a drain pump. Use a carpenter’s level to check Hole-in-plug Insert Concrete...
  • Page 389 Placing the Unit Inside the Ceiling This unit is equipped with the drain pump. Check a tape measure or carpenter’s level. Ceiling Before installing the ceiling panel, complete the work of conditioner drain pipe and refrigerant pipe installation. (1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale Paper model for installation...
  • Page 390 Installing the Drain Pipe Before Performing the Installation Drain Piping (1) Limitations of Raising the Drain Pipe Connection 300 mm or less (as short as possible) CAUTION Indoor unit A : 850 mm or lower Ceiling surface The drain pipe can be raised to a maximum height of B : 670 mm or lower 850 mm from the bottom surface of the ceiling.
  • Page 391 Installing the Drain Pipe CAUTION Do not apply force to the drain port when connecting the 3) Move the hose band so that the center position of the drain pipe. Install and fix it near the indoor unit as close hose band can be placed approx.
  • Page 392 Checking the Drainage Be careful since the fan will start Drainage check CAUTION when you short the pin on the indoor control board. After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up Over 100 mm spilled water.
  • Page 393 Important Note for Wiring 4-Way Cassette Type Power supply inlet (1) The power supply inlet is located at the lower area of the refrigerant tubing side of the unit. The electrical component box is located at the air intake of the bottom of the unit.
  • Page 394 How to Install the Ceiling Panel (3) Installing the ceiling panel The power must be turned ON in order to change the (1) Removing the air-intake grille flap angle. (Do not attempt to move the flap by hand. 1) Remove the 2 screws on the latch of the air-intake Doing so may damage the flap.) grille.
  • Page 395 (5) How to Attach the Corner & Air-Intake Grille A. Attaching the corner cover CAUTION 1) Check that the safety cord from the corner cover is fastened to the ceiling panel pin, as shown in the figure If the screws are not sufficiently tightened, trouble below.
  • Page 396 Others 2) When setting with the Wired Remote Controller (1) Checking After Installation <Procedure> 1) Check that there are no gaps between the unit and Stop the system before performing these steps. the ceiling panel, or between the ceiling panel and the Press and hold the buttons ceiling surface.
  • Page 397 (4) Setting the Flap Separately (When setting the CZ-RTC2) Press the timer time buttons to select the 1) The 4-air outlet flap can be adjusted separately during desired setting data. operation. When not adjusted separately, all flaps Flap position operate in the same manner. Air discharge port Flap...
  • Page 398 (4-Way Cassette) Part Name Figure Q’ty Remarks Full-scale Printed on installation container box diagram For suspension Washer bolts For full-scale Screw installation diagram For gas and liquid (White) Insulating tape tube flare nuts Flare insulator For liquid tube Flare insulator For gas tube Drain hose For securing drain...
  • Page 399: Selecting The Installation Site 4-Way Cassette Type (U1)

    2. SELECTING THE INSTALLATION SITE HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette 60×60 Type (Y1) 4-Way Cassette 60 × 60 Type Indoor Unit (Y1 Type) AVOID: Preparation for Ceiling Suspension areas where leakage of flammable gas may be expected. This unit uses a drain pump.
  • Page 400 Placing the Unit Inside the Ceiling Twist tie (4 ties, supplied) (1) When placing the unit inside the ceiling, determine the Hard PVC pipe Drain hose Position to (equivalent to pitch of the suspension bolts using the supplied full-scale Drain port insulation fasten hose O.D.
  • Page 401 (4-Way Cassette 60 × 60) 300 mm or less Part Name Figure Q'ty Remarks 850 mm or less 0 - 45° For temporarily Washer suspending indoor unit from ceiling * Length of supplied drain hose = 140 mm Fig. 2-8 Do not use natural drainage.
  • Page 402: How To Install The Ceiling Panel

    HOW TO INSTALL THE CEILING PANEL Before Installing the Ceiling Panel (1) Remove the air-intake grille and air filter from the ceiling panel. 4-Way Cassette 60 × 60 Type (Y1 Type) a) Remove the 2 screws on the latch of the air-intake Checking the unit position grille.
  • Page 403 The ceiling panel must be installed in the correct direction Wiring the Ceiling Panel relative to the unit. Align the REF. PIPE and DRAIN marks (1) Open the cover of the electrical component box. on the ceiling panel corner with the correct positions on the (2) Connect the 7P wiring connector (red) from the ceiling unit.
  • Page 404 Adjusting the Auto Flap Hole for ceiling The air-direction louver on the ceiling panel outlet can be panel hook adjusted as follows. Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping mechanism.
  • Page 405: Selecting The Installation Site Ceiling Type (T1)

    3. SELECTING THE INSTALLATION SITE Ceiling Ceiling Type (T1) Ceiling Indoor Unit AVOID: areas where leakage of flammable gas may be expected. Wall places where large amounts of oil mist exist. direct sunlight. Font view locations near heat sources which may affect the performance of the unit.
  • Page 406 HOW TO INSTALL THE INDOOR UNIT Ceiling Type (T1 Type) Air intake Required Minimum Space for Installation and Service Ceiling side (1) Dimensions of suspension bolt pitch and unit Length Type 36, 45, 50 27.5 27.5 (Suspension bolt pitch) 60, 71 1125 1180 Unit: mm...
  • Page 407 (4) Wall and ceiling side opening position WARNING Figure shows view from front. It is important that you use extreme care in supporting the indoor unit from the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before Ceiling hanging the ceiling unit, test the strength of each attached suspension bolt.
  • Page 408 Suspension bolt PVC pipe (field supply) (field supply) INSIDE OUTSIDE Washer Wall (field supply) PVC pipe Unit Slight Washer (supplied) angle Double nut (field supply) Cut at slight angle Fig. 3-12 Fig. 3-17 Duct for Fresh Air There is a duct connection port (knock-out hole) at the right-rear of the top panel of the indoor unit for drawing in fresh air.
  • Page 409 (Ceiling) Part Name Figure Q’ty Remarks For temporarily Special suspending indoor unit washer from ceiling Drain For drain hose joint insulator For gas and liquid tube Flare insulator sets joints Insulating For gas and liquid flare White tape joints (heat- resisting) For flare and drain Vinyl clamp...
  • Page 410: Selecting The Installation Site Ceiling Type (T2)

    4. SELECTING THE INSTALLATION SITE Ceiling Ceiling Type (T2) Indoor Unit Ceiling AVOID: areas where leakage of flammable gas may be expected. Wall places where large amounts of oil mist exist. direct sunlight. locations near heat sources which may affect the Minimum 25 cm Minimum 25 cm performance of the unit.
  • Page 411 Unit: mm HOW TO INSTALL THE INDOOR UNIT Ceiling Type (T2 Type) 4-1. Required Minimum Space for Installation and Service Air intake (1) Dimensions of suspension bolt pitch and unit Length Type 36, 45, 50 60, 71 1226 1275 100, 125, 140 1541 1590 Unit: mm...
  • Page 412 4-2. Preparation Before Installation (4) Remove the center bracket. When wiring, remove the center bracket if necessary. (1) Remove the bracket (for suspending the indoor unit). When wiring is completed, reinstall the center bracket in its Loose the M8 suspension bolts. original position.
  • Page 413 b) Suspend the indoor unit to the bracket. WARNING Tighten the M8 suspension bolts and fix the indoor unit in place. (Fig. 4-17) It is important that you use extreme care in supporting the indoor unit from the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit.
  • Page 414 4-5. Shaping the Tubing Never allow water traps to occur in the course of the piping. Insulate any piping inside the room to prevent dripping. The positions of the refrigerant tubing connections are After the drain piping, pour an appropriate amount of water shown in the figure below.
  • Page 415 4-7. Final Procedure ( Ceiling ) Reinstall the removed part to be placed in its original position. Part Name Figure Q’ty Remarks (See the section “4-2. Preparation Before Installation”.) For temporarily suspending Special Then install the accessory supplied side covers (L/R) on both indoor unit from ceiling washer sides of the indoor unit.
  • Page 416: Selecting The Installation Site Wall Mounted Type (K1)

    5. SELECTING THE INSTALLATION SITE Wall Mounted Wall Mounted Type (K1) Indoor Unit AVOID: min. 7.5 cm min. min. areas where leakage of flammable gas may be expected. 5 cm 5 cm places where large amounts of oil mist exist. direct sunlight.
  • Page 417 HOW TO INSTALL THE INDOOR UNIT Wall Mounted Type (K1 Type) Remove the Rear Panel from the Unit (1) Remove and discard the set screw on the rear panel. (Fig. 5-1) (2) Press the 2 marks on the frame cover and disengage the stationary tabs from the frame.
  • Page 418 (4) Using a sabre saw, key hole saw or hole-cutting drill N OT E attachment, cut a hole in the wall. See Table 5-1 and Hole should be made at a slight downward slant to the outdoor Fig. 5-7. side. Indoor Outdoor Table 5-1...
  • Page 419 Removing and Installing the Grille Front panel Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps as given below. How to remove the grille (1) Open the front panel until it is nearly horizontal, grasp the sections near the front panel arms on both sides, and then remove the panel by pushing the arms towards the outside while pulling the panel towards you.
  • Page 420 Shape the Indoor Side Tubing (1) Arrangement of tubing by direction a) Right or left tubing Cut out the corner of the right/left frame with a hacksaw or the like. (Figs. 5-19 and 5-20) Grille b) Right-rear or left-rear tubing In this case, the corner of the frame need not be cut.
  • Page 421 Mounting (1) To install the indoor unit, mount the indoor unit onto the 3 tabs on the upper part of the rear plate. (2) Hold down the air discharge outlet and press the lower part of the indoor unit until it clicks to securely fasten to the 2 tabs on the lower part of the rear plate.
  • Page 422 Left-side tubing (1) Lead the tubing and drain hose through the wall, allowing sufficient length for connection. Then bend the tubing using a tube bender to make the attachment. (Fig. 5-28) Rear panel (2) Switch the drain hose and drain cap. Hole in wall Switching drain hose and drain cap (a) Locate the drain hose and the drain cap.
  • Page 423 To unmount indoor unit (1) Remove the screw cover on the bottom surface. (Fig. 5-34) (2) Fasten the frame to the rear panel using the 2 supplied tapping screws 4 × 10 mm. (Fig. 5-34) (3) Press the 2 marks on the lower part of the indoor unit and unlatch the tabs.
  • Page 424 (Wall Mounted) Part Name Figure Q’ty Truss-head Phillips Tapping screw 4 × 20 mm Truss-head Phillips Tapping screw 4 × 10 mm Flare insulation 1-414...
  • Page 425: Selecting The Installation Site Low Silhouette Ducted Type (F1)

    6. SELECTING THE INSTALLATION SITE Low Silhouette Ducted Type (F1) Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near heat sources which may affect the performance of the unit.
  • Page 426 HOW TO INSTALL THE INDOOR UNIT Low Silhouette Ducted Type (F1 Type) Unit: mm 6-1. Required Minimum Space for Installation and Service A (Suspension bolt pitch) This air conditioner is usually installed above the ceiling so Electrical that the indoor unit and ducts are not visible. Only the air component box intake and air outlet ports are visible from the unit bottom.
  • Page 427 6-2. Suspending the Indoor Unit Suspension bolt Depending on the ceiling type: • Insert suspension bolts (Fig. 6-3) Nuts and washers (use for upper and lower) • Use existing ceiling supports or construct a suitable support (Fig. 6-4). Suspension lug Hole-in-anchor Concrete Insert...
  • Page 428 6-3. Installing the Drain Pipe 300 mm or less (1) Prepare standard hard PVC pipe (O.D. 32 mm) for the 500 mm or less drain and use the supplied hose band to prevent water Good leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage.
  • Page 429 6-4. Connecting Duct to Air Intake Port Side Bracket (1) First pull out a filter in the direction of the electrical equipment box in the unit. (Fig. 6-15) The pre-installed filter will not be used any more. (2) Then remove the seal packing, bracket and filter attached to the side of the air intake port.
  • Page 430 6-5. External Static Pressure Setting Choose one of the following methods from “a”, “b”, “c” or “d” as shown in the flow chart (within the dotted lines) and then make the setting accordingly. a. No setting modification............: Use-as-is at shipment (there are cases in which the setting may differ from the shipment setting when reset after once setting the external static pressure.) b.
  • Page 431 Refer to Table 6-4 and Fig. 6-18 for details on the relationship between the value of item code “b0” and the external stati c pressure. When set in group control (connecting multiple indoor units with one wired remote controller), set each indoor unit to item code “b0”.
  • Page 432 6-7. Operating the Timer Remote Controller (CZ-RTC2) Table 6-4 Setting the external static pressure Setting Item Code “ ” Indoor unit Item code 36, 45, 50, 60, 71 100, 125, 140 Press and hold down the buttons External static pressure of the rated simultaneously for 4 or more seconds.
  • Page 433 Indoor Fan Performance Item code “ ” M M M M M M M L L L L L L L L 1 -2 L L L L 1 -3 100 type 36, 45 types PQ diagram PQ diagram 1 -3 1 -2 1 -3 1 -2...
  • Page 434 (Low Silhouette Ducted) Part Name Figure Q’ty Remarks For suspending indoor Washer unit from ceiling Flare insulator For gas and liquid tubes Insulating For gas and liquid tubes tape flare nuts Drain For drain hose joint insulator Hose band For securing drain hose For drain hose joint Packing (hard material)
  • Page 435 Optional Duct Frange How to Install Duct Frange 4 circle duct frange (CZ-160DAF2) 3 circle duct frange (CZ-90DAF2) 2 circle duct frange (CZ-56DAF2) 1. Remove the air outlet duct frange. 2. Attach the duct frange to the side of the unit with the supplied screws. Duct frange 1-425...
  • Page 436 Dimensional Diagram : CZ-56DAF2 unit: mm Ø200 Ø200 (45) (170) Dimensional Diagram : CZ-90DAF2 unit: mm Ø200 Ø200 Ø200 (45) Dimensional Diagram : CZ-160DAF2 unit: mm Ø200 Ø200 Ø200 Ø200 1240 (45) (185) 1-426...
  • Page 437: Selecting The Installation Site Ducted Type (N1)

    7. SELECTING THE INSTALLATION SITE Ducted Type (N1) Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near heat sources which may affect the performance of the unit. locations where external air may enter the room directly.
  • Page 438 SELECTING THE LOCATION FOR THE INDOOR UNIT 7-1. Required Minimum Space for Installation and Service Provide a check port on the piping side ceiling for repair and maintenance. Install the indoor unit once the following conditions are satisfied and after receiving the customer approval. The indoor unit must be within a maintenance space.
  • Page 439 NOTE NAME Q'TY Pipe connection (gas) O.D. Ø12.7 Flared Pipe connection (liquid) O.D. Ø6.35 Flared Drain pipe connection Female screw PT1" Duct connection Hanger Control box 650 (P65 x 10) Air Flow 22-Ø4.5 24-Ø4.5 585 (P65 x 9) Air Flow UNIT:mm S-36PN1E5 Drain pipe connection...
  • Page 440 NOTE NAME Q'TY Pipe connection (gas) O.D. Ø15.88 Flared Pipe connection (liquid) O.D. Ø9.52 Flared Drain pipe connection Female screw PT1" Duct connection Hanger Control box 1260 1160 1040(P65x16) 44-Ø4.5 46-Ø4.5 975 (P65 x 15) 57.5 1090 Air Flow 1320 1200 Drain pipe connection UNIT:mm...
  • Page 441 7-2. Suspending the Indoor Unit Depending on the ceiling type: • Insert suspension bolts (Fig. 7-3) • Use existing ceiling supports or construct a suitable support (Fig. 7-4). Hole-in-anchor Hole-in-plug Concrete Insert Ceiling tiles Ceiling support Suspension bolt (M10 or 3/8") (field supply) Fig.
  • Page 442 7-3. Installing the Drain Pipe Drainage hole (1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. Thermal insulator Hose clip (Accessories) CAUTION (Accessories)
  • Page 443 7-5. External Static Pressure Setting for Dc Fan Motor Model Choose one of the following methods from “a”, “b”, “c” or “d” as shown in the flow chart (within the dotted lines) and then make the setting accordingly. a. No setting modification............: Use-as-is at shipment (there are cases in which the setting may differ from the shipment setting when reset after once setting the external static pressure.) b.
  • Page 444 Refer to Table 7-3 and Fig. 7-18 for details on the relationship between the value of item code “b0” and the external static pressure. When set in group control (connecting multiple indoor units with one wired remote controller), set each indoor unit to item code “b0”. When amending the setting after selecting [ b.
  • Page 445 7-7. Operating the Timer Remote Controller (CZ-RTC2) Table 7-3 Setting the external static pressure Setting Item Code “ ” Indoor unit Item code Press and hold down the buttons 60, 71 100, 125, 140 simultaneously for 4 or more seconds. External static pressure of the rated , the Unit No., Item Code and Detailed Data will air flow volume (Pa)
  • Page 446 Indoor Fan Performance Item code “ ” M M M M M M M 1 -2 1 -3 S-60PN1E5 • S-71PN1E5 S-125PN1E5 P-Q diagram P-Q diagram Limit line Limit line Air Volume (m /min.) Air Volume (m /min.) S-100PN1E5 S-140PN1E5 P-Q diagram P-Q diagram Limit line...
  • Page 447 7-8. External Static Pressure Setting for AC Fan Motor Model To apply to following models S-36PN1E5 , S-45PN1E5 , S-50PN1E5 There are two tap connector located in indoor unit control box can be selected. The “blue connector” is standard tap, use-as-is at shipment. For high static pressure duct, switch Fan Motor connector to plug in boost tap “white connector”...
  • Page 448 (Ducted) Part Name Figure Q’ty Remarks For suspending indoor unit Washer from ceiling Flare insulator For gas and liquid tubes Hose band For securing drain hose Foam drain For drain hole socket (another side of drain hose) Drain hose Flange For inlet duct installation Screw Use M10 for suspension bolts.
  • Page 449: How To Select Ahu System

    1-12. How to select AHU system AHU system selection guideline System lineup Capacity Outdoor combination Connectable AHU-kit combination 10 kW U-100PE1E8 U-100PE1E5 CZ-280PAH1 CZ-280PAH1 12.5 kW U-125PE1E8 U-125PE1E5 CZ-280PAH1 CZ-280PAH1 14 kW U-140PE1E8 U-140PE1E5 CZ-280PAH1 CZ-280PAH1 * Single connection type only * Mix connection with standard indoor units is not allowed.
  • Page 450 Installation   Installation of Strainer (Field supplied) Attach the strainer to the side of the outdoor unit for Gas & Liquid piping. (See the “System Overview” on previous page.) Thermistor for Liquid pipe and Heat exchanger pipe middle Liquid pipe thermistor Attach the liquid pipe thermistor Cover the thermistor Cover the aluminum...
  • Page 451 Blower operation signal and protection signal Blower signal output Power supply Minimum applicable load DC 5 V, 1 mA Maximum applicable load AC 230 V, 2 A X1 : Relay (field supply) Blower protect input SW 1 : operation command (field supply) AC 220 ~240 V, 0.1 A Limitation of AHU When the AHU is selected, there are some limitations.
  • Page 452 Restriction on the number of passes of the heat exchanger hairpin Minimum number of passes = Number of steps × Distance between tube sheets × Number of rows × 1.5 ×10 <For example> Number of steps Distance between tube sheets 1000 [mm] Number of rows Minimum number of passes = 12 ×...
  • Page 453: Capacity Table

    1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 454 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 455 14.8 4.68 13.8 4.87 10.1 3.98 230V 13.6 13.6 3.86 13.6 13.6 4.15 13.1 13.1 4.41 12.2 12.2 4.59 3.75 S-45PU1E5×3 240V U-125PE1E5 14.6 12.1 4.03 14.6 12.2 4.32 14.0 11.8 4.60 13.0 11.5 4.78 3.91 50Hz (U-125PE1E8) 16.0 4.16 16.0...
  • Page 456 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 457 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 458 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 459 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 460 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceilling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 461 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 462 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 463 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 464 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 465 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 466 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 467 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 468 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 469 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 470 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C...
  • Page 471 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 472 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 473 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 474 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 475 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 476 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 477 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 478 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 46°C Source...
  • Page 479 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C...
  • Page 480 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C...
  • Page 481 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C...
  • Page 482 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 483 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 484 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 485 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 486 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 487 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 488 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C...
  • Page 489 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C...
  • Page 490 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 491 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 492 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
  • Page 493 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 494 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 495 1-13. Capacity Table :Cooling Capacity SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C 43°C Source...
  • Page 496: Heating Capacity Performance Data

    1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.79 1.84 2.19...
  • Page 497 15.0 5.28 15.0 4.65 15.0 3.94 (3 phase) 220V 16.7 5.52 17.2 5.43 17.3 4.91 17.3 4.33 17.3 3.66 230V S-45PU1E5×3 240V U-125PE1E5 15.5 5.84 15.9 5.74 16.0 5.20 16.0 4.58 16.0 3.87 50Hz (U-125PE1E8) 1 phase 14.5 5.93 14.9 5.84...
  • Page 498 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 2.00 2.06...
  • Page 499 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88...
  • Page 500 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 2.03 2.08 2.47 2.96...
  • Page 501 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88 2.90 2.86...
  • Page 502 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.79 1.84 2.19 2.62...
  • Page 503 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88 2.90 2.86...
  • Page 504 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.91 1.96 2.33...
  • Page 505 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88 2.90...
  • Page 506 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Sihouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.87 1.92...
  • Page 507 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88...
  • Page 508 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.96 2.02 2.39 2.87...
  • Page 509 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.90 2.92 2.88...
  • Page 510 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.89 1.92 2.05...
  • Page 511 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.95 2.04 2.38...
  • Page 512 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit 4-Way Cassette 60×60 Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 2.09 2.19...
  • Page 513 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.89 1.92 2.05 2.29...
  • Page 514 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 2.02 2.11 2.47 2.68...
  • Page 515 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.89 1.92 2.05 2.29...
  • Page 516 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Ceiling Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.95 2.04 2.38 2.59...
  • Page 517 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.92 1.96 2.09...
  • Page 518 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Wall Mounted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.98 2.07 2.42...
  • Page 519 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.80 1.83...
  • Page 520 1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5&#