4-4. Connecting Duct to Air Intake Port Side
(1) First pull out a filter in the direction of the electrical
component box in the unit. (Fig. 1-104)
The pre-installed filter will not be used any more.
(2) Then remove the seal packing, bracket and filter attached
to the side of the air intake port. (Fig. 1-104)
(3) Install the duct (field supply).
See the figure for the dimension of the installation hole.
Use M5 self-tapping screws for installation. (Fig. 1-105)
NOTE
• Select an air-intake grille with a filter at a local shop.
• To get clean air and to extend the service life of the air
conditioner, an air filter must be installed in the air intake.
For installation and cleaning the air filter, consult your dealer
or service center.
Filter
H
Type
G
600
36, 45, 50
(Pitch 150 × 4)
900
60, 71
(Pitch 150 × 6)
1,350
100, 125, 140
(Pitch 150 × 9)
1-352
Bracket
Packing
G
H
J
Unit : mm
H
J
K
25
113
14
25
13
18
0
13
24
Fig. 1-104