Specifications; A-1-1 Ratings - Omron E5C User Manual

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

A Appendices
A-1 Specifications
A-1-1
Ratings
Supply voltage
Operating voltage range
E5CC/E5CC-U
E5EC
Power
consumption
E5AC
E5DC
*1
Sensor input
Relay
output
Control output
*4
1/2
Voltage
output
Linear current
output
Auxiliary output
Relay outputs
Control method
Setting method
Indication method
Other functions
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
*1
For input setting ranges, refer to A-7 Sensor Input Setting Range, Indication Range, Control Range.
*2
When connecting the ES2-HB/THB, connect it 1:1.
*3
With the E5CC, you cannot select a relay output or linear current output for control output 2.
*4
The E5CC-U and E5DC do not have control output 2.
A - 2
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
Option number 000: 5.2 VA max.
Other option numbers: 6.5 VA max.
Option number 000: 6.6 VA max.
Other option numbers: 8.3 VA max.
Option number 000: 7.0 VA max.
Other option numbers: 9.0 VA max.
4.9 VA max.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: Pt100, JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
*2
: 4 to 20 mA, 0 to 20 mA (Input impedance: 150 Ω max.)
Current input
*2
Voltage input
: 1 to 5 V, 0 to 5 V, 0 to 10 V (Input impedance: 1 MΩ min.)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
E5CC/
E5DC
Min. applicable load: 5 V, 10 mA
SPDT, 250 VAC, 3 A (resistive load), electrical durability: 100,000 operations
E5CC-U
Min. applicable load: 5 V, 10 mA
E5EC/
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations
E5AC
Min. applicable load: 5 V, 10 mA
Output voltage 12 VDC ±20% (PNP), max. load current 21 mA, with short-circuit protection
E5CC/
E5CC-U
circuit
/E5DC
Control Output 1
Output voltage 12 VDC ±20% (PNP), max. load current 40 mA, with short-circuit protection
circuit
E5EC/E
(21 mA if there are two control outputs)
5AC
Control Output 2
Control output 2: 12 VDC ±20% (PNP), max. load current 21 mA, with short-circuit protection
circuit
4 to 20 mA DC, 0 to 20 mA DC, Load: 500 Ω max.
Resolution: Approx. 10,000
1 auxiliary output (E5CC-U) or 2 auxiliary outputs (E5CC, E5CC-U, E5EC, or E5AC)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
Min. applicable load: 5 V, 10 mA
Two Auxiliary Outputs (E5DC), Three Auxiliary Outputs (E5CC), or Four Auxiliary Outputs
(E5EC)
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations,
Min. applicable load: 5 V, 10 mA
ON/OFF or 2-PID control (with autotuning)
Digital setting using front panel keys
11-segment digital displays and individual indicators
Depend on the model
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C (with no
condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time lag, low shut-off capacity
Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)
24 VAC, 50/60 Hz/24 VDC
Option number 000: 3.1 VA max./1.6 W max.
Other option numbers: 4.1 VA max./2.3 W max.
Option number 000: 4.1 VA max./2.3 W max.
Other option numbers: 5.5 VA max./3.2 W max.
Option number 000: 4.2 VA max./2.4 W max.
Other option numbers: 5.6 VA max./3.4 W max.
2.8 VA max./1.5 W max.
*3
*3
E5@C Digital Temperature Controllers User's Manual (H174)

Advertisement

Table of Contents
loading

This manual is also suitable for:

H174-e1-05 series