6 Parameters
oc-h
• The Open/Close Hysteresis parameter is used to shift the ON and OFF points for the
open output and close output to prevent output chattering.
Function
Setting
Related Parameters
See
See
Position Proportional Dead Band (Adjustment Level): Page 6-35
sqrp
• This parameter sets the extraction of square root low-cut point used for the inputs. The
data after extracting the square root is shown below.
• The low-cut point is used for extracting the square root for flowrate sensors.
Function
Setting
Related Parameters
See
See
Extraction of Square Root Enable (Initial Setting Level): Page 6-58
6 - 36
Open/Close Hysteresis
Setting range
0.1 to 20.0
Extraction of Square Root Low-cut
000
Point
Operation result
100% FS
Setting range
0.0 to 100.0
A Position-proportional Model must be used.
Unit
%
The input type must be an analog input, and the
Extraction of Square Root Enable parameter must
be set to ON.
Extraction of square
root low-cut point
100% FS
0
Argument 1 (input data)
Unit
Default
%
0.0
E5@C Digital Temperature Controllers User's Manual (H174)
Default
0.8