Communications
RS-485
Models with an option number of 002 to 004, 008, 009, 012, 014, or 015 support RS-485 communications.
Connect the communications cable to terminals 13 and 14 to use communications with the E5CC, E5AC, or
E5EC. Connect the communications cable to terminals 3 and 4 to use communications with the E5DC.
Communications Unit Connection Diagram
E5CC/E5EC/E5AC
Host computer
RS-485
+
100 Ω
FG
A < B: [1] Mark
A > B: [0] Space
E5DC
RS-485
host computer
+
100 Ω
FG
A < B: "1" Mark
A > B: [0] Space
• The RS-485 connection can be either one-to-one or one-to-N. A maximum of 32 Units (including
the host computer) can be connected in one-to-N systems. The maximum total cable length is
500 m. Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205 to 0.823 mm
twisted-pair cable.
Note: The E5CC-U does not support communications.
E5@C Digital Temperature Controllers User's Manual (H174)
Shield
E5CC/E5EC/E5AC (No. 1)
RS-485
No.
Abbreviation
14
A (−)
B (+)
13
Terminator (120 Ω, 1/2 W)
Shield
E5DC (No. 1)
RS-485
No. Abbreviation
A( − )
4
3
B(+)
Cross-sectional area of
conductor
2
AWG24: 0.205 mm
2
AWG18: 0.823 mm
E5CC/E5EC/E5AC
(No. 31)
RS-485
No.
Abbreviation
14
A (−)
B (+)
13
E5DC (No. 31)
RS-485
No. Abbreviation
A( − )
4
3
B(+)
Terminator (120 Ω, 1/2 W)
2 Preparations
2
2
)
2 - 35