Omron E5C User Manual page 262

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

6 Parameters
ptrn
This parameter sets the type of control when using the simple program function.
• If the program pattern is set to off, the simple program will not operate.
• If the program pattern is set to stop, the RUN/STOP status will change to STOP after the
soak time has expired. If the program pattern is set to cont, control will continue in RUN
Function
status after the soak time has expired.
Setting
Related Parameters
See
See
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
RUN/STOP (Operation Level) : Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Soak Time Unit (Advanced Function Setting Level): Page 6-80
cp
c-cp
• These parameters set the output periods. Set the control periods taking the control
characteristics and the electrical life of the relay into consideration.
• For standard control, use the Control Period (Heating) parameter. The Control Period
Function
(Cooling) parameter cannot be used.
• When the heating control output is a current output, the Control Period (Heating)
parameter cannot be used.
• For heating/cooling control, the control period can be set independently for heating and
cooling. The Control Period (Heating) parameter is used for the heating control output,
and the Control Period (Cooling) parameter is used for the cooling control output.
Parameter name
Control Period
Setting
(Heating)
Control Period
(Cooling)
Related Parameters
See
See
PID ON/OFF (Initial Setting Level): Page 6-44
6 - 46
000
Program Pattern
off
Simple program function turned OFF
stop
Go to STOP mode at end of program.
cont
Continue in RUN mode at end of program.
Control Period (Heating)
Control Period (Cooling)
Setting range
0.1, 0.2, 0.5, 1 to 99
0.1, 0.2, 0.5, 1 to 99
Setting range
The cooling control output and heating control
output must be assigned to relay or voltage
outputs (for driving SSR).
The control must be set to 2-PID control.
For the Control Period (Cooling) parameter, the
control must be set to heating/cooling control.
Unit
Seconds
Seconds
E5@C Digital Temperature Controllers User's Manual (H174)
Default
off
Default
20 for relay output
2 for voltage output (for driving SSR)
20 for relay output
2 for voltage output (for driving SSR)