Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

sptr
• This parameter sets the operation to perform when moving from Remote SP Mode to
Local SP Mode.
• When this parameter is set to ON, operation continues using the remote SP as the local
Function
SP.
• When this parameter is set to OFF, the remote SP does not affect the local SP.
Setting
Related Parameters
See
See
Set Point During SP Ramp (Operation Level): Page 6-10
SP Mode (Adjustment Level): Page 6-21
p-db
When the PV enters the PV dead band, any unnecessary output is stopped to prevent the
valve from deteriorating.
Function
SP
PV
Setting
Related Parameters
See
See
Close/Floating, Motor Calibration, and Travel Time (Initial Setting Level): Page 6-57
Position Proportional Dead Band (Adjustment Level): Page 6-35, Open/Close Hysteresis
(Adjustment Level): Page 6-36
E5@C Digital Temperature Controllers User's Manual (H174)
000
SP Tracking
Setting range
on: Enabled or off: Disabled
PV Dead Band
Unnecessary output is
stopped in this range.
Setting range
0 to 9999
There must be a remote SP input.
The ST parameter must be set to OFF.
The Remote SP Enable parameter must be set to
ON.
Default
off
A Position-proportional Model must be used.
PV Dead Band
Unit
Default
EU
0
6 Parameters
6
6 - 83