6-7

Initial Setting Level

This level is used to set up the basic Digital Controller specifications. In this level, you can set the Input
Type parameter to set the sensor input to be connected, limit the setting range of set points, set the
alarm modes, and perform other operations.
Power ON
Operation
Level
25
Press the
O Key
100
for at
Press the O Key
least 1 s.
for at least 3 s.
Initial Setting
Level

Initial Setting Level

Page
Input Type
in-t
6-42
s
M
in-h
Scaling Upper
6-43
Limit
100
M
Scaling Lower
in-l
6-43
Limit
0
M
Decimal Point
dp
6-43
0
M
d-u
Temperature Unit
6-43
c
M
SP Upper Limit
sl-h
6-44
1300
M
SP Lower Limit
sl-l
6-44
-200
M
PID·ON/OFF
cntl
6-44
onof
M
Standard or
s-hc
6-45
Heating/Cooling
stnd
M
ST
st
6-45
on
M
Program Pattern
ptrn
6-46
000
off
M
Control
cp
6-46
Period (Heating)
20
M
Control Period
c-cp
6-46
(Cooling)
20
M
E5@C Digital Temperature Controllers User's Manual (H174)
Press the O Key for at
least 1 s; display will flash.
Control stops.
Control in progress
Control stopped
orev
Direct/Reverse
Operation
or-r
M
Alarm 1 Type
alt1
2
M
Alarm 1
alh1
Hysteresis
0.2
M
Alarm 2 Type
alt2
2
M
alh2
Alarm 2
Hysteresis
0.2
M
alt3
Alarm 3 Type
2
M
Alarm 3
alh3
Hysteresis
0.2
M
Alarm 4 Type
alt4
2
M
Alarm 4
alh4
Hysteresis
0.2
M
Control Output 1
o1st
Signal
4-20
M
Control Output 2
o2st
Signal
4-20
M
Transfer Output
trst
Signal
4-20
M
Transfer Output
tr-t
Type
off
M
To move from the Operation Level to the Initial Set-
ting Level, press the O Key for at least three sec-
onds with any parameter displayed except for the
Auto/Manual Switch parameter.
• The Initial Setting Level is not displayed when the
Initial Setting/Communications Protect parameter
is set to 2. It can be used when the Initial
Setting/Communications Protect parameter is set
to 0 or 1.
• If the Input Type parameter is set for an analog
input, the following parameters will be set: Scaling
upper limit, Scaling lower limit, and Decimal point.
Page
6-47
6-47
6-51
6-47
6-51
6-47
6-51
6-47
6-51
6-52
6-52
000
6-53
000
6-52
000
6 Parameters
Page
Transfer Output
tr-h
6-54
Upper Limit
100.0
000
M
Transfer Output
tr-l
6-54
Lower Limit
0.0
000
M
Event Input
ev-1
6-55
Assignment 1
msp0
M
Event Input
ev-2
6-55
Assignment 2
stop
M
Event Input
ev-3
6-55
Assignment 3
none
M
Event Input
ev-4
6-55
Assignment 4
none
M
Event Input
ev-5
6-55
Assignment 5
none
000
M
Event Input
ev-6
6-55
Assignment 6
none
000
M
Close/Floating
clfl
6-57
flo t
M
Motor Calibration
calb
6-57
off
M
Travel Time
mot
6-58
30
M
Extraction of
sqr
6-58
Square Root
off
Enable
000
M
Move to Advanced
amov
6-58
Function Setting
0
Level
M
6 - 41
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

H174-e1-05 series