Omron E5C User Manual page 261

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

s-hc
• This parameter selects standard control or heating/cooling control.
• When heating/cooling control is used on the E5CC, E5CC-U, or E5DC and there is only
one control output, auxiliary output 2 (SUB2) is allocated as the control output for cooling.
Function
(If the Controller has only one auxiliary output, an output is not automatically allocated for
the control output for cooling).
• If heating/cooling control is selected for the E5EC/E5AC when there is only one control
output, the auxiliary output 4 terminal (SUB4) is assigned as the control output for
cooling.
Note: If standard control is selected, set the Control Output 1 Assignment to o (control output
(heating)) for either direct (cooling) or reverse (heating) operation.
Setting
Related Parameters
See
See
MV Monitor (Heating) (Operation Level): Page 6-16
MV Monitor (Cooling) (Operation Level): Page 6-16
Dead Band (Adjustment Level): Page 6-30
Hysteresis (Heating) and Hysteresis (Cooling) (Adjustment Level): Page 6-31
Control Period (Heating) and Control Period (Cooling) (Initial Setting Level): Page 6-46
Control Output 1 and 2 Assignment (Advanced Function Setting Level): Page 6-78
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-79
st
• The ST (self-tuning) function executes tuning from the start of program execution to
calculate PID constants matched to the control target. When the ST function is in
operation, be sure to turn ON the power supply of the load connected to the control output
Function
simultaneously with or before starting E5@C operation.
• Auto-tuning can be started during self-tuning.
off: ST function OFF, on: ST function ON
Setting
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-42
PID ON/OFF (Initial Setting Level): Page 6-44
ST Stable Range (Advanced Function Setting Level): Page 6-65
E5@C Digital Temperature Controllers User's Manual (H174)
Standard or Heating/Cooling
Setting range
stnd: Standard, h-c: Heating/cooling
ST (self-tuning)
Setting range
A Standard Model must be used.
Default
stnd
The control must be set to a temperature input,
standard control, and 2-PID control.
Default
on
6 Parameters
6
6 - 45

Advertisement

Table of Contents
loading

This manual is also suitable for:

H174-e1-05 series

Table of Contents