Omron E5C User Manual page 42

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

2 Preparations
E5EC/E5AC
E53-COV24
Terminal Cover
Waterproof packing
Mounting to the Panel
(1) For waterproof mounting, waterproof packing must be installed on the Controller.
Waterproofing is not possible when group mounting several Controllers. Waterproof
packing is not necessary when there is no need for the waterproofing function.
(2) Insert the E5EC/E5AC into the mounting hole in the panel.
(3) Push the Adapter from the terminals up to the panel, and temporarily fasten the
E5EC/E5AC.
(4) Tighten the two fastening screws on the Adapter. Alternately tighten the two screws little by
little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
2 - 8
• E53-COV17
Terminal Cover
(E53-COV17)
(Sold separately.)
Adapter
Panel
Adapter
*
The Terminal Cover is provided only with the
following models: E5EC-@@@@5M-@@@.
E5@C Digital Temperature Controllers User's Manual (H174)
• E53-COV23
Enlarged Illustration of
Terminal Section
Adapter
E53-COV24
Terminal Cover*

Advertisement

Table of Contents
loading

This manual is also suitable for:

H174-e1-05 series

Table of Contents