4 Basic Operation
4-2

Initial Setting Examples

Initial hardware setup, including the sensor input type, alarm types, control periods, and other settings,
is done using parameter displays. The O and M Keys are used to switch between parameters, and the
amount of time that you press the keys determines which parameter you move to.
This section describes three typical examples.
Explanation of Examples
Changing Parameters
in-t
in-h
0
M
in-l
intl
intl
onof
Example 1
Input type:
Control method: ON/OFF control
Alarm type:
Alarm value 1:
Set point:
*
If the Controller is equipped with HB/HS alarm detection, the Alarm 1 Type is not displayed for the default
settings. To use alarm 1, set an output assignment to alarm 1. For details, refer to 4-6-3 Assigned Output
Functions (Assigning Control Outputs Is Not Supported for Position-proportional Models.).
4 - 8
A
image means that there are parameters.
Continue pressing the M Key to change parameters
until you reach the intended parameter.
M
100
M
0
Changing Numbers
Numeric data and selections in each
25
screen can be changed by using the
0
onof
U and D Keys.
Setup Procedure
Power ON
5 (K thermocouple, −200°C to 1,300°C)
2 (upper limit)
20°C (deviation)
100°C
Initial Setting Level
Set input
specifications
Set control
specifications
Set alarm type
Operation Level
Set SP and alarm values
Start operation
Power ON
Operation Level
PV/SP
25
0
Press the O Key for at least 3 s.
Control stops.
Initial Setting Level
in-t
Input Type: 5
Check input type.
5
M
Check that
cntl
ON/OFF
control method is
control:
onof
ON/OFF control.
PID control:
M
alt1
Check alarm type.
Alarm 1 Type*: 2
2
M
Press the O Key for at least 1 s.
Control starts.
Operation Level
25
Use the U and
PV/SP:
D Keys to set the
100
SP to 100°C.
M
r-5
Confirm that
Running
control is running.
run
Stopped:
M
al-1
Use the U and
Alarm Value 1:
D Keys to set the
20
alarm value to
20°C.
M
Start operation.
E5@C Digital Temperature Controllers User's Manual (H174)
An s.err error will be
displayed if the power
supply is turned ON before
the sensor is connected.
onof
pid
100
run
stop
20