6 Parameters
c-db
This parameter sets the output dead band width for heating/cooling control. A negative setting sets an
overlapping band.
• This parameter sets an area in which the control output is 0 centering around the set point
for a heating/cooling control.
Function
Temperature input
Setting
Analog input
of-r
• This parameter sets the required manipulated variable to remove offset during
stabilization of P or PD control.
Function
Setting
Related Parameters
See
See
Integral Time (Adjustment Level): Page 6-28
PID ON/OFF (Initial Setting Level): Page 6-44
6 - 30
Dead Band
Setting range
−199.9 to 999.9
−19.99 to 99.99
Manual Reset Value
Setting range
0.0 to 100.0
The control system must be set to heating/cooling
control.
Unit
°C or °F
%FS
The control must be standard control and 2-PID
control.
The Integral Time parameter must be set to 0.
Unit
Default
%
50.0
E5@C Digital Temperature Controllers User's Manual (H174)
Default
0.0
0.00