Specifications; A-1-1 Ratings - Omron E5CC-800 User Manual

Digital temperature controllers
Hide thumbs Also See for E5CC-800:
Table of Contents

Advertisement

A Appendices
A-1 Specifications
A-1-1
Ratings
Supply voltage
Operating voltage range
E5CC
Power
consumption
E5EC
*1
Sensor input
Relay
output
Control output 1/2
Voltage
output
Current output
Auxiliary output
Relay outputs
Control method
Setting method
Indication method
Other functions
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
*1
For input setting ranges, refer to A-6 Sensor Input Setting Range, Indication Range, Control Range.
*2
When connecting the ES2-HB/THB, connect it 1:1.
HB and HS Alarms
(E5CC/E5EC Models with HB and HS Alarms)
Max. heater current
Input current readout accuracy
Heater burnout alarm setting
range
Heater short alarm setting
range
*1
HB alarms are not detected and the heater power is not measured if the ON time for the control output for
heating is 100 ms or less (30 ms or less if the control period is 0.1 or 0.2 s).
*2
HS alarms are not detected and the leakage power is not measured if the ON time for the control output
for heating is 100 ms or less (35 ms or less if the control period is 0.1 or 0.2 s).
A - 2
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
Option number 800: 5.2 VA max.
Other option numbers: 6.5 VA max.
Option number 800: 6.6 VA max.
Other option numbers: 8.3 VA max.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: Pt100, JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
*2
: 4 to 20 mA, 0 to 20 mA (Input impedance: 150 Ω max.)
Current input
*2
Voltage input
: 1 to 5 V, 0 to 5 V, 0 to 10 V (Input impedance: 1 MΩ min.)
SPST-NO, 250 VAC, 3 A (resistive load), electrical durability: 100,000 operations
E5CC
Min. applicable load: 5 V, 10 mA
SPST-NO, 250 VAC, 5 A (resistive load), electrical durability: 100,000 operations
E5EC
Min. applicable load: 5 V, 10 mA
Output voltage 12 VDC ±20% (PNP), max. load current 21 mA, with short-circuit protection
E5CC
circuit
Output voltage 12 VDC ±20% (PNP), max. load current 40 mA, with short-circuit protection
E5EC
circuit (21 mA if there are two control outputs)
4 to 20 mA DC, 0 to 20 mA DC, Load: 500 Ω max.
Resolution: Approx. 10,000
SPST-NO, 250 VAC, 3 A (resistive load), electrical durability: 100,000 operations
Min. applicable load: 5 V, 10 mA
2-PID or ON/OFF control
Digital setting using front panel keys
11-segment digital displays and individual indicators
Depend on the model
−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time lag, low shut-off capacity
Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (0.1 A units)
0.0 A:
Heater burnout alarm output turns OFF.
50.0 A:
Heater burnout alarm output turns ON.
Min. detection ON time
0.1 to 49.9 A (0.1 A units)
0.0 A:
Heater short alarm output turns ON.
50.0 A:
Heater short alarm output turns OFF.
Min. detection OFF time
24 VAC, 50/60 Hz/24 VDC
Option number 800: 3.1 VA max./1.6 W max.
Other option numbers: 4.1 VA max./2.3 W max.
Option number 800: 4.1 VA max./2.3 W max.
Other option numbers: 5.5 VA max./3.2 W max.
*1
:
30 ms for a control period of 0.1 s or 0.2 s
100 ms for a control period of 0.5 s or 1 to 99 s
*2
:
35 ms for a control period of 0.1 s or 0.2 s
100 ms for a control period of 0.5 s or 1 to 99 s
Digital Temperature Controllers (Simple Type) User's Manual (H211)

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ec-800

Table of Contents