Chapter 4
Monitoring Settings
4.6
Transmission Test Execution
2
Check the result of the test transmission.
Check that the SNMP Trap is notified to the monitoring server.
For details on the messages for test transmission, refer to "Message List".
If the SNMP Manager cannot receive an SNMP test trap, check that the network has no trouble, and the
settings for the ETERNUS DX are correct.
Is the LAN between the monitoring server and ETERNUS DX connected correctly?
Execute the "ping" command from the monitoring server, and confirm the reply from the ETERNUS
DX.
When "ICMP" is disabled by the firewall settings for ETERNUS Web GUI, the "ping" command cannot
be used for confirmation. Enable "ICMP" before executing the "ping" command.
Is the monitoring software set correctly to monitor the ETERNUS DX?
Are the SNMP environment settings and the transmission destination for the SNMP Trap set correctly
on the ETERNUS DX?
4.6.2

Send Test Mail

Perform the email transmission test to check that the email can be sent from the ETERNUS DX to the speci-
fied email address.
The procedure to send test mail is as follows:
1
On the navigation of the ETERNUS Web GUI screen, click [System].
The [System] screen appears.
2
In [Category], click [Network].
The [Network] screen appears.
3
In [Action], click [Setup E-Mail Notification].
The [Setup E-Mail Notification] screen appears.
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Configuration Guide (Basic)
80
Copyright 2014 FUJITSU LIMITED
P3AM-7732-05ENZ0