Wiring

2.1 Wiring

2.1.1

Terminal connection diagram

Sink logic
Main circuit terminal
Control circuit terminal
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary
with the input terminal
assignment
(Pr. 178 to Pr. 189)
(Refer to page 133)
Start self-holding selection
Multi-speed
selection
Second function selection
*3. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
*5
* 4. Terminal input specifications
can be changed by analog
input specifications switchover
(Pr. 73, Pr. 267). Set the
voltage/current input switch in
the OFF position to select
voltage input (0 to 5V/0 to
10V) and ON to select current
input (0 to 20mA).
(Refer to page 185)
* 5. It is recommended to use
2W1k
when the
frequency setting signal is
changed frequently.
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the
main circuit wire of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc. take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Operation with a wrong setting may cause a fault, failure or malfunction.
14
*1. DC reactor (FR-HEL)
Be sure to connect the DC reactor
supplied with the 75K or higher.
When a DC reactor is connected
to the 55K or lower, remove the
jumper across P1 and P/+.
MC
MCCB
Jumper
*2
Earth
(Ground)
Forward
rotation
start
Reverse
rotation
start
High speed
Middle speed
Low speed
Jog operation
Output stop
Reset
power failure
24VDC power supply
3
2
1
Auxiliary
(+)
(-)
input
Terminal
(+)
4 input
(-)
(Current
input)
Connector
for plug-in option
connection
*1
Earth
Jumper
Jumper
(ground)
P1
P/+
PR
PX
*7
*7
R/L1
Inrush current
S/L2
limit circuit
T/L3
ON
EMC filter
R1/L11
ON/OFF
S1/L21
OFF
connector
*8
Main circuit
Control circuit
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
*3
AU
AU
PTC
CS
SD
24V
PC
PU
connector
*4
Voltage/current
input switch
4 2
10E(+10V)
ON
10(+5V)
OFF
Initial value
0 to 5VDC
2
0 to 10VDC selectable
* 4
0 to 20mADC
5
(Analog common)
Initial
0 to ± 10VDC
value
1
* 4
0 to ± 5VDC
selectable
Initial
4 to 20mADC
value
4
0 to 5VDC
* 4
selectable
0 to 10VDC
Option connector 1
Terminating
resistor
Resistor unit
*6. A CN8 (for MT-BU5)
(Option)
connector is provided
Brake unit
with the 75K or higher.
(Option)
*7.
Do not use PR and PX terminals.
Please do not remove the jumper
connected to terminal PR and PX.
N/-
CN8
*6
U
V
W
*8. The 200V class 0.75K and 1.5K
are not provided with the ON/OFF
connector EMC filter.
C1
Terminal functions
B1
vary with the output
Relay output 1
terminal assignment
(Pr. 195, Pr. 196)
(Fault output)
A1
(Refer to page 140)
C2
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
(Pr. 190 to Pr. 194)
IPF
Instantaneous
(Refer to page 140)
power failure
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink / source common
* 9. It is not necessary
when calibrating the
indicator from the
operation panel.
+
-
FM
Calibration
resistor * 9
SD
(+)
AM
Analog signal output
(0 to 10VDC)
5
(-)
RS-485 terminals
TXD+
Data transmission
TXD-
RXD+
Data reception
RXD-
SG
GND
5V
(Permissible load
VCC
current 100mA)
Motor
M
Earth
(ground)
cable
Relay output
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale

Hide quick links:

Advertisement

Table of Contents
loading